SterlingTEK A0551797 manual Staging, Alarms, Lead-Lag Compressors, Lead-Lag Pumps

Page 27

4

Sequence Of Operation

 

 

4-1 Staging

1.The system uses a PID control algorithm to regulate the chilled water temperature. As the required control effort increases or decreases, the system compressors are turned on or off to keep the temperature at the specified set-point

2.Compressor anti-recycle time is three (3) minutes.

4-2 Alarms

If a fault occurs, that compressor or circuit is deactivated. The load will automatically shift to any other compressors that are currently ON-LINE, but not running. Lead/Lag rotation will continue to function. Compressors that are faulted will be removed from the rotation order.

4-3 Lead-Lag Compressors

The system automatically rotates the compressor order to generate a Lead/Lag rotation. Any time a compressor is faulted or manually taken OFF-LINE, it will be removed from the Lead/Lag rotation.

Once the fault is cleared or manually put ON-LINE, the compressor is returned to the Lead/Lag rotation at the end of the rotation order.

4-4 Lead-Lag Pumps

The system automatically rotates the pump order to generate a Lead/Lag rotation. Any time a pump is faulted or manually taken OFF-LINE, it will be removed from the Lead/Lag rotation. Once the fault is cleared or manually put ON-LINE, the pump is returned to the Lead/Lag rotation at the end of the rotation order.

SSC Series Central Chilling Stations

Page 27 of 86

Image 27
Contents SSC Series Central Chilling Stations SSC Series Central Chilling Stations Wear Safety Glasses and Work Gloves Safety ConsiderationsTable of Contents Getting Started on the SSC Series Advanced Touchscreen Startup ChecklistsCharts and Figures Necessary Documents IntroductionModels Covered Standard FeaturesAvailable Options Standard Features on Remote CondensersModel Number Nomeclature Model SSCW-xxx Typical Two-Circuit 60-100 Ton Water Cooled ChillerCooling Capacity tons @ 50F 10 C LWT 73.1 81.4 Model SSCR-xxx Typical Two-Circuit 60-100 Ton Remote Air Cooled ChillerSscr Series Remote Condenser Models Event of Shipping Damages Unpacking and InspectionIf the Shipment is Not Complete If the Shipment is Not CorrectReturns Uncrating Your New Chiller SSC Series Central Chilling Stations 3Installation Installation Location ConsiderationsMaking Electrical Connections SSC Series Central Chilling Stations Piping Considerations Making Process Water ConnectionsAll Models From Process Making Tank Piping ConnectionsMaking Water-Cooled Condenser Connections Water Connection Sizing ConsiderationsGalvanic Corrosion Considerations Water Treatment Considerations Condenser Water Installing the Remote Air-Cooled CondenserCompressor Checking Motor DirectionSSC Series Central Chilling Stations Lead-Lag Pumps AlarmsStaging Lead-Lag CompressorsChilled Water Circuit Refrigeration CircuitFreezestat Control Freezing Protection Curve VolumeFlow Switch High Pressure CutoutLow Pressure Cutout Condenser Water Manifold Control NippleControl Probe Chilled Water ManifoldSSC Series Central Chilling Stations Water-Cooled SSC Series Startup Checklist Startup ChecklistsSSC Series Central Chilling Stations Water-Cooled SSC Series Startup Remote Air-Cooled SSC Series Startup ChecklistSSC Series Central Chilling Stations Remote Air-Cooled SSC Series Startup Shutdown Determining Flow RateSSC Series Central Chilling Stations SSC Series Central Chilling Stations Graphic Panel Devices Indicator Lights and Control Switches MMISSC Series Central Chilling Stations Using the Standard Touchscreen InterfaceTouchscreen Interface Introduction MMI SSC Series Standard Control Panel Using the SSC Series Standard Touchscreen InterfaceMain Menu Screen Viewing and Operating Chiller Compressors Viewing Compressor StatusCompressor Status Screen Operating the chiller compressors Chiller Configuration ScreenCompressor Lead/Lag Screen Compressor Enable ScreenCompressor Run Time Display Screen Viewing Compressor Run TimesViewing and Operating Chiller Pumps Viewing Chiller Pump StatusPump Status Screen Operating Chiller Pumps Pump Enables ScreenViewing Pump Run Times Pump Lead/Lag ScreenPump Run Time Display Screen Alarm Condition Screen Viewing Active Alarms and Handling Alarm ConditionsOr Death Setting System Temperatures Viewing and Setting System TemperaturesSSC Series Central Chilling Stations Using the Advanced Using the SSC Series Advanced Touchscreen Interface Main Menu Screen Viewing and Operating Chiller Compressors Chiller Status Screen Operating the chiller compressors Viewing Compressor Run Times Viewing and Operating Chiller Pumps Viewing Chiller Pump Status Operating Chiller Pumps Hourmeters Pump Run Time screen displays Viewing Active Alarms and Handling Alarm Conditions Alarm Condition Screen Or Death System Status Screen Temperature Input Display Screen Lubrication Condenser MaintenanceRecommended Pump Tank Spare Parts Evaporator MaintenancePump Motor Seal Makeup ValvePreventive Maintenance Service SSC Series Central Chilling Stations Problem Possible Cause Solution 10TroubleshootingAllow time to cool and reset Verify proper rotation if Service Notes Index Water Treatment Service Notes Service Notes Service Notes Sterling Th Street New Berlin, WI 262 641-8610 ∙ Fax 262 Parts Department