þCheck for proper pump rotation direction. To confirm proper rotation:

1.Observe a pump pressure gauge connected to the suction and discharge sides of the pump casing through two ¼” (approx. 6.4 mm) gauge cocks.

2.Close the gauge cock leading to the pump suction and open the gauge cock leading to the pump discharge.

3.Close the discharge butterfly valve, crack it open, then start the pump and observe the gauge.

If the gauge indicates within 15 psi (103.4 kPa/1.03 bars) below the pump curve, pump rotation is correct. Pump rotation is clockwise opposite the shaft end.

If the gauge indicates 20 psi (137.9 kPa/1.38 bars) or more below the pump curve, the pump is running backwards. Reverse rotation by interchanging any two power mains to the pump motor or starter.

Recheck the pressure to be sure it increased.

þCheck the water level in the pump tank to be sure the pump does not run dry while the system piping is being filled.

þCheck your work and proceed to the Startup procedure in the following section.

5-5 Remote Air-Cooled SSC Series Startup

1.Start the chiller by pushing the Start button on the control panel of the unit.

2.The touchscreen will display the Main Menu screen.

3.If your chiller has been setup to control the pump tank, the recirculation pump will turn on first, then after 5 seconds the process pump will turn on. If configured with a standby pump, the lead/lag will control which pump turns on.

4.Fifteen (15) seconds after the last pump turns on the first compressor will turn on. Based on the temperature of the water, the controller will turn on compressors every 15 seconds.

5.Adjust the Freezestat cut-out, located in the main electrical enclosure, to 10°F (6ºC) below the process temperature set point you want.

SSC Series Central Chilling Stations

Page 37 of 86

Image 37
Contents SSC Series Central Chilling Stations SSC Series Central Chilling Stations Wear Safety Glasses and Work Gloves Safety ConsiderationsTable of Contents Getting Started on the SSC Series Advanced Touchscreen Startup ChecklistsCharts and Figures Necessary Documents IntroductionModels Covered Standard FeaturesAvailable Options Standard Features on Remote CondensersModel Number Nomeclature Model SSCW-xxx Typical Two-Circuit 60-100 Ton Water Cooled ChillerCooling Capacity tons @ 50F 10 C LWT 73.1 81.4 Model SSCR-xxx Typical Two-Circuit 60-100 Ton Remote Air Cooled ChillerSscr Series Remote Condenser Models Event of Shipping Damages Unpacking and InspectionIf the Shipment is Not Correct If the Shipment is Not CompleteReturns Uncrating Your New Chiller SSC Series Central Chilling Stations Installation Location Considerations 3InstallationMaking Electrical Connections SSC Series Central Chilling Stations Making Process Water Connections Piping ConsiderationsAll Models From Process Making Tank Piping ConnectionsGalvanic Corrosion Considerations Water Connection Sizing ConsiderationsWater Treatment Considerations Making Water-Cooled Condenser ConnectionsCondenser Water Installing the Remote Air-Cooled CondenserCompressor Checking Motor DirectionSSC Series Central Chilling Stations Staging AlarmsLead-Lag Compressors Lead-Lag PumpsRefrigeration Circuit Chilled Water CircuitFreezestat Control Freezing Protection Curve VolumeHigh Pressure Cutout Flow SwitchLow Pressure Cutout Control Probe Control NippleChilled Water Manifold Condenser Water ManifoldSSC Series Central Chilling Stations Water-Cooled SSC Series Startup Checklist Startup ChecklistsSSC Series Central Chilling Stations Water-Cooled SSC Series Startup Remote Air-Cooled SSC Series Startup ChecklistSSC Series Central Chilling Stations Remote Air-Cooled SSC Series Startup Shutdown Determining Flow RateSSC Series Central Chilling Stations SSC Series Central Chilling Stations Graphic Panel Devices Indicator Lights and Control Switches MMISSC Series Central Chilling Stations Touchscreen Interface Using the StandardTouchscreen Interface Introduction MMI SSC Series Standard Control Panel Using the SSC Series Standard Touchscreen InterfaceMain Menu Screen Viewing Compressor Status Viewing and Operating Chiller CompressorsCompressor Status Screen Operating the chiller compressors Chiller Configuration ScreenCompressor Lead/Lag Screen Compressor Enable ScreenCompressor Run Time Display Screen Viewing Compressor Run TimesViewing Chiller Pump Status Viewing and Operating Chiller PumpsPump Status Screen Operating Chiller Pumps Pump Enables ScreenPump Lead/Lag Screen Viewing Pump Run TimesPump Run Time Display Screen Alarm Condition Screen Viewing Active Alarms and Handling Alarm ConditionsOr Death Setting System Temperatures Viewing and Setting System TemperaturesSSC Series Central Chilling Stations Using the Advanced Using the SSC Series Advanced Touchscreen Interface Main Menu Screen Viewing and Operating Chiller Compressors Chiller Status Screen Operating the chiller compressors Viewing Compressor Run Times Viewing and Operating Chiller Pumps Viewing Chiller Pump Status Operating Chiller Pumps Hourmeters Pump Run Time screen displays Viewing Active Alarms and Handling Alarm Conditions Alarm Condition Screen Or Death System Status Screen Temperature Input Display Screen Lubrication Condenser MaintenancePump Motor Seal Evaporator MaintenanceMakeup Valve Recommended Pump Tank Spare PartsPreventive Maintenance Service SSC Series Central Chilling Stations Problem Possible Cause Solution 10TroubleshootingAllow time to cool and reset Verify proper rotation if Service Notes Index Water Treatment Service Notes Service Notes Service Notes Sterling Th Street New Berlin, WI 262 641-8610 ∙ Fax 262 Parts Department