Advanced Controller Programming (Cont.)
Auxiliary Relay Mode
The Auxiliary Relay has normally open and normally closed contacts. The factory setting disables the Auxiliary Relay. The relay can be set for:
• Maglock: To deactivate a magnetic or solenoid gate lock, the relay |
will energize during any pending or actual gate motion (open only). |
• M4: To deactivate a magnetic or solenoid gate lock, the relay will |
energize during any pending or actual gate motion (open only). |
3 seconds after the gate starts to move, the relay will |
This option is used for higher current solenoid locks. |
• Ticket Dispenser: The relay will energize while the gate is moving |
in the open direction and at the full open limit, or in an entrapment |
condition. |
• Strobe: To activate a warning strobe light, the relay will energize |
during any pending or actual gate motion (either open or close). |
FUNCTION
"AR"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO SELECT AN OPTION
AUXILIARY
RELAY MODE
OPTIONS
AUXILIARY RELAY DISABLED
AUXILIARY RELAY USED FOR
MAGLOCK CONTROL
AUXILIARY RELAY USED FOR
MAGLOCK OR SOLENOID CONTROL 3 SECOND DELAY TO
AUXILIARY RELAY USED FOR
TICKET DISPENSER CONTROL
AUXILIARY RELAY USED FOR
WARNING STROBE LIGHT
AUXILIARY RELAY USED FOR
CONNECTION TO ALARM DEVICE
• Alarm: The relay will energize if the gate is manually forced open |
from the full closed position. |
Reverse Delay Time
The factory default sets the Reverse Delay to 1 second. The operator will wait the length of the delay before reversing direction. This feature will not change the reversal time when the operator is responding to an entrapment condition from an obstruction input or inherent entrapment protection sensor. The Reverse Delay can be set from 1 to 9 seconds. Heaver gates require a longer delay to allow time for the gate to stop.
FUNCTION |
| OPTIONS | |||||
|
|
| "RD" |
|
|
| SET TIMER VALUE |
|
|
|
|
|
| ||
|
|
|
|
|
| 1 TO 9 SECONDS | |
|
|
|
|
|
|
|
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
REVERSE
DELAY TIME
Brake Delay Time
This function is displayed,but only used in operators with mechanical brakes. The Model
The factory default sets the Brake Delay to no delay (0 seconds). Heavy gates may require delayed braking to allow the gate to slow down before stopping it. The operator can be set to wait the length of the delay after running before applying the brake. The Brake Delay can be set from 0 to 3 seconds.
Constant Pressure Mode
The factory default allows momentary pressure on a control station’s OPEN or CLOSE button to cycle the operator. The controller can be set
FUNCTION
"BD"
BRAKE
DELAY TIME
OPTIONS
SET TIMER VALUE 0 TO 3 SECONDS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
to require constant pressure on the OPEN, CLOSE, or both buttons to run the operator.
✓NOTE: If a button is set for constant pressure, and it is released before the operator reaches the open or close limit, the operator will stop the gate at its current position.
Shadow Loop Open Prevention
If the shadow loop is triggered, it always prevents the gate from closing if the Auto Close Timer activates or a CLOSE command is given while the gate is at the full open position.
FUNCTION
"CP"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO SELECT AN OPTION
CONSTANT
PRESSURE MODE
OPTIONS
CONSTANT PRESSURE SET TO OFF (MOMENTARY PRESSURE ON)
OPEN BUTTON SET FOR
CONSTANT PRESSURE
CLOSE BUTTON SET FOR
CONSTANT PRESSURE
OPEN AND CLOSE BUTTONS BOTH SET FOR CONSTANT PRESSURE
The controller can also be set to prevent the gate from opening if the shadow loop is triggered while the gate is at the close limit position. This prevents a swing gate from opening into a vehicle if it’s parked near the gate on the inside.
| FUNCTION |
| OPTIONS | |||||
|
|
|
| "SP" |
|
|
| STANDARD OPERATION |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| SHADOW LOOP INHIBITS CLOSING ONLY | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| OPEN INHIBIT ON, SHADOW LOOP INHIBITS |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| OPENING AND CLOSING |
|
|
|
|
| PRESS UP OR | |||
|
|
|
|
| DOWN TO CYCLE | |||
|
|
|
|
| THROUGH OPTIONS | |||
|
|
|
|
|
|
|
|
|
| SHADOW LOOP | PRESS ENTER TO | ||||||
OPEN PREVENTION | SELECT AN OPTION | |||||||
|
|
|
|
- 15 - | P1250 Revision X6 | |
|