Linear SLR, SLD, SLC Auxiliary Relay Mode, Reverse Delay Time, Low Power Mode, Power Failure Mode

Page 16

Advanced Controller Programming (Cont.)

Auxiliary Relay Mode

The Auxiliary Relay has normally open and normally closed contacts. The factory setting disables the Auxiliary Relay. The relay can be set for:

• Maglock: The relay will energize during any pending or actual gate

motion (open only), to deactivate a magnetic or solenoid gate lock.

• Ticket Dispenser: The relay will energize while the gate is moving

in the open direction and at the full open limit, or in an entrapment

condition.

• Strobe: The relay will energize during any pending or actual gate

motion (either open or close), to activate a warning strobe light.

• Alarm: The relay will energize if the gate is manually forced open

from the full closed position.

FUNCTION

"AR"

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

AUXILIARY

RELAY MODE

OPTIONS

AUXILIARY RELAY DISABLED

AUXILIARY RELAY USED FOR

MAGLOCK CONTROL

AUXILIARY RELAY USED FOR

TICKET DISPENSER CONTROL

AUXILIARY RELAY USED FOR

WARNING STROBE LIGHT

AUXILIARY RELAY USED FOR

CONNECTION TO ALARM DEVICE

Reverse Delay Time

The factory default sets the Reverse Delay to 1 second. The operator will wait the length of the delay before reversing direction. This feature will not change the reversal time when the operator is responding to an entrapment condition from an obstruction input or inherent entrapment protection sensor. The Reverse Delay can be set from 1 to 9 seconds. Heaver gates require a longer delay to allow time for the gate to stop.

Low Power Mode

This function is only used with DC slide gate Model SLD. The factory default disables the Low Power Mode.When Low Power Mode is enabled,

FUNCTION

"RD"

REVERSE

DELAY TIME

OPTIONS

SET TIMER VALUE 1 TO 9 SECONDS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

and AC power fails, the controller will assume Low Power Mode after 60 seconds of gate inactivity. Low power mode turns off all accessory power and indicators. Only inputs from the radio receiver, reverse loop, or restoring AC power will wake the Controller from Low Power Mode. Programming Mode can still be accessed while the Controller is in Low Power Mode.

NOTE: This function will only be displayed in Model SLD operators.

Power Failure Mode

This function is only used with DC slide gate Model SLD. The factory default is set for Fail Safe, alternately the Controller can be set for Fail Secure, Open Immediate, or Close Immediate.

 

FUNCTION

 

OPTIONS

 

 

 

 

 

"LP"

 

 

 

LOW POWER MODE DISABLED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW POWER MODE ENABLED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESS UP OR

 

 

 

 

 

 

DOWN TO CYCLE

 

 

 

 

 

 

THROUGH OPTIONS

 

 

 

 

 

 

 

 

 

 

 

 

LOW POWER

PRESS ENTER TO

DC MODELS

 

 

MODE

SELECT AN OPTION

ONLY

 

 

 

 

 

 

Fail Safe: If the AC power fails and the battery voltage drops below approximately 22 Volts, 5 seconds later the operator will cycle open if not already open. When AC power is restored, or the battery gets charged by solar panels, the operator will resume normal operation and autoclose if programmed to do so.

Fail Secure: If the AC power fails and the battery voltage drops below approximately 22 Volts, 5 seconds later the operator will cycle closed if not already closed. When AC power is restored, or the battery gets charged by solar panels, the operator will resume normal operation.

NOTE: Fail Safe and Fail Secure are disabled if Stagger Mode is enabled.

Open Immediate: If the AC power fails, the operator will cycle open if not already open and cease operation. When AC power is restored, the operator will resume normal operation and auto-close if programmed to do so.

Close Immediate: If the AC power fails, the operator will cycle closed if not already closed and cease operation. When AC power is restored, the operator will resume normal operation.

NOTE: This function will only be displayed in Model SLD operators.

FUNCTION

"FS"

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO SELECT AN OPTION

POWER

FAILURE MODE

OPTIONS

SET TO FAIL SAFE MODE

SET TO FAIL SECURE MODE

SET TO OPEN IMMEDIATE MODE

SET TO CLOSE

DC MODELS

IMMEDIATE MODE

ONLY

 

SLR SLC SLD  Slide Gate Operator Installation Guide

- 14 -

227968 Revision X13 2-3-09

Image 16
Contents SLR SLC SLD Table of Contents Before You Begin Always Check the Gate’s ActionRegulatory Warnings Gate Operator ClassificationsAC Power Wiring Wiring SpecificationsDC Control and Accessory Wiring Mounting Pad Installation Mounting Pad SpecificationsGate Preparation Gate PostGate Bracket and Chain Assembly END of Gate Pipe Shown Reference onlyOperator Setup Operator PreparationLimit Nuts Fine Adjustment Limit Nuts Rough AdjustmentRIGHT-HAND Installation Controller Features ConnectorsIndicator Descriptions Blinks if Connection has Failed Maint Alert SETTerminal Descriptions Terminal Group FunctionOperator Accessory Connections Operator Accessory ConnectionsBasic Controller Programming Maximum Open Direction Current Setting Run Alarm and Pre-start AlarmMaximum Close Direction Current Setting Entering Advanced Programming Mode Single Button Input SetupAdvanced Controller Programming Maximum Run TimeAuxiliary Relay Mode Reverse Delay TimeLow Power Mode Power Failure ModeReset Cycle Count Maintenance Alert TriggerSoft Start/Stop Duration Mid-travel Stop PositionRadio Enable Antenna InstallationReset Controller to Factory Defaults Radio Transmitter LearnLoop Layout Illustration Loop SealantUSE Relief Cuts AT Corners SLR SLC SLD Safety Edge Layout Illustration Safety Edge Layout Illustration #2 Photoeye Installation Illustration Entrapment Zone #3 Pickets Space Smaller than 2 1/4Entrapment Zone #1 Track Gate Installation Gate Bracket Bolted to ChannelDual Gate Installations Open and Close Limit settingsOperator #1 ShieldGate Operation Operation IndicationsError Indications EntrapmentComm Link Connection Failure MGT Obstacle Transmitter TroubleTroubleshooting Model SLR Exploded View Optional PartsModel SLC Exploded View Optional Torque LimiterFor drives 34 to 47 feet wide CapacitorsModel SLD Exploded View LimiterModel SLD Mechanical Parts List Model SLD Maintenance Battery MaintenanceDC Motor Brush Replacement When NEWPreventative Maintenance Month Preventative MaintenanceFCC Notice GeneralGate Operator Installation Checklist Installer Customer