GE FVR-C9S-2UX Drive Series Installation Instructions, Wiring, Installation Conditions

Page 13

FVR-C9S-2UX

6. Installation Instructions

Installation Conditions

Install the drive in a location which meets the following requirements:

The ambient temperature should be be- tween -10°C and +50°C.

The humidity should be between 20 and 90% RH. Avoid any location subject to dew condensation, freezing or where the drive could come into contact with any liquids.

Mounting plate: Heat sink temperature will reach +90°C during operation. Please use thermostable material for drive mounting plate.

Multi-mounting:When 2 or more drives are installed within the drive switchboard, ar- range them side by side, keeping space (shown in the above figure) between each drive. If the drives must be lined up vertically, provide adequate ventilation so that the hot air from each drive will not affect the one above it.

Do not install in any location subject to any of the following conditions: direct sunlight, dust, corrosive gas, inflammable gas or oil mist.

The drive should be installed at an eleva- tion below 3283 feet (1000m), and vibra- tion should be less than 232 inches/s2 (5.9m/s2)

7 Wiring

Perform wiring in accordance with the fol- lowing procedure:

1)Remove the cover mounting screw at the center of the cover.

Mounting Direction and Space

3.94”

(10cm)

 

PRG

RUN

 

RESET

 

 

 

FUNC

STOP

 

DATA

 

 

 

 

FVR-C9S

0.394”

 

0.394”

(1cm)

 

(1cm)

CLOSED OPEN

3.94”

(10cm)

NOTICE: The durability and reliability of the drive will be affected by the ambient tem- perature. Do not place the unit where ambi- ent temperature is not proper.

Direction: Insert M4 size screws in the mounting screw holes in the left upper and right lower of the drive, and install the drive with these screws. Install the drive vertically. Horizontal or other positional installation will cause the drive to overheat.

Space: The drive will generate heat during operation. Allow sufficient space around the unit as shown in the above figure.

PRG

RUN

RESET

 

FUNC

STOP

DATA

 

FVR-C9S

CLOSED OPEN

Cover Mounting Screw

2)Hold the lower end of the cover, lift it up and remove the cover

2

1

Side view of inverter

3)Remove the keypad panel from the main unit, and disconnect the harness from the CN2 at the same time.

13

Image 13
Contents FVR-C9S-2UX Drive Series Product specifications are subject to change without notice Contents Wiring Fire and Electric Shock Hazard Safety PrecautionsOperation Electric Shock Hazard Nameplate Inspection Upon ReceiptType Part NamesInput power Voltage/frequency Supply voltage 3% SpecificationsType FVR C9S-2UX F12 F25 F50 DWG 1 FVRF12C9S-2UX to FVROO1C9S-2UX External DimensionsDWG 2 FVR002C9S to FVR003C9S-2UX FVR005C9S-2UX Wiring Installation InstructionsInstallation Conditions Mounting Direction and SpaceDisconnect CRG Lamp 30C Basic Wiring DiagramsKeypad Panel Operation FAB External Signal OperationApplicable motor output Hp Drive type Application of Wiring and EquipmentTerminal Function Explanation Terminal Function ExplanationTerminal Function Explanation Operation Frequency Setting MethodPre-Operation Inspection Test Run Check PointsRUN/STOP Selecting Operation MethodPart Names and Functions Keypad PanelControlling Method for Keypad Panel Function setting method Function Code Tables Function ExplanationMotor Running Code 2 Operation Command 1 Frequency Command0 Data Protection 3 Maximum Frequency8 Electronic Thermal Overload Relay Torque BoostElectronic Thermal Overload Relay Level Low High30% 2 DC Brake 1 Gain for Frequency Setting Signal3 DC Brake Braking Time 4 Starting Frequency 6 Fault Memory5 Motor Running Sound 7 Data Initialization 9 Motor Characteristics8 Retry Jump Frequency Range6 Bias Frequency 4 High Limiter F 2 5 Low Limiter7 THR Terminal Function 8 BX Terminal FunctionMultistep Speed Setting 2 Speed Multistep Speed Setting 1 SpeedMultistep Speed Setting 3 Speed 3 FM Terminal Function Selection 2 FM Terminal Output Level CalibrationOC3 Protective FunctionsTechnical Services GE Fuji Drives USA, Inc Warranty Parts and ServiceOut-of-Warranty Procedures MotorsLatest Fault Previous Faults No Message In-Warranty Failure ChecklistFVR-C9S-2UX FVR-C9S-2UX FVR-C9S-2UX