GE FVR-C9S-2UX Drive Series Pre-Operation Inspection, Test Run Check Points, RUN/STOP Method

Page 20

FVR-C9S-2UX

11. Operation

Pre-Operation Inspection

Check for wiring errors.

Check that all loose wire stands, metal chips and unnecessary screws, etc. have been removed.

Check that no screws, terminals, etc. are loose.

Check that the wire ends of crimp terminal are not in contact with other terminals.

The drive is shipped with a factory in- stalled jumper, between FWD-CM. Only forward operation is possible. To enable reverse operation remove the jumper from FWD/CM and install the jumper between REV-CM.

RUN/STOP by terminal operation (F02 : 1)

Note) Open FWD and REV terminals when changing F02 data. Data cannot be changed if not open.

Test Run Check Points

Smooth rotation and correct rotation direction.

No abnormal vibrations and noise from the motor.

Smooth acceleration and deceleration.

Frequency Setting Method

Frequency setting by potentiometer con- trol (factory preset at the time of shipment; F01:1). As wired at the factory, frequency setting can be performed by turning the potentiometer control knob on the keypad panel. Turn the potentiometer control knob clockwise to increase frequency.

Frequency setting by digital signal (F01 : 0). With the function F01 set to 0, fre- quency can be increased or decreased by the

UP/DOWN) keys on the keypad panel. UP: Frequency up

DOWN: Frequency down

RUN/STOP Method

RUN/STOP by keypad panel operation (Factory preset at the time of shipment F02:0).

Frequency

RUN

Frequency

FWD-CM

REV-CM

STOP Time

Forward

Reverse

ON

ON

20

Image 20
Contents FVR-C9S-2UX Drive Series Product specifications are subject to change without notice Contents Safety Precautions Wiring Fire and Electric Shock HazardOperation Electric Shock Hazard Inspection Upon Receipt NameplatePart Names TypeSpecifications Input power Voltage/frequency Supply voltage 3%Type FVR C9S-2UX F12 F25 F50 External Dimensions DWG 1 FVRF12C9S-2UX to FVROO1C9S-2UXDWG 2 FVR002C9S to FVR003C9S-2UX FVR005C9S-2UX Installation Instructions WiringInstallation Conditions Mounting Direction and SpaceDisconnect CRG Lamp Keypad Panel Operation Basic Wiring Diagrams30C External Signal Operation FABApplication of Wiring and Equipment Applicable motor output Hp Drive typeTerminal Function Explanation Terminal Function ExplanationTerminal Function Explanation Frequency Setting Method OperationPre-Operation Inspection Test Run Check PointsSelecting Operation Method RUN/STOPControlling Method for Keypad Panel Keypad PanelPart Names and Functions Function setting method Function Explanation Function Code TablesMotor Running Code 1 Frequency Command 2 Operation Command0 Data Protection 3 Maximum FrequencyTorque Boost 8 Electronic Thermal Overload RelayElectronic Thermal Overload Relay Level Low High30% 3 DC Brake Braking Time 1 Gain for Frequency Setting Signal2 DC Brake 5 Motor Running Sound 6 Fault Memory4 Starting Frequency 9 Motor Characteristics 7 Data Initialization8 Retry Jump Frequency Range4 High Limiter F 2 5 Low Limiter 6 Bias Frequency7 THR Terminal Function 8 BX Terminal FunctionMultistep Speed Setting 3 Speed Multistep Speed Setting 1 SpeedMultistep Speed Setting 2 Speed 2 FM Terminal Output Level Calibration 3 FM Terminal Function SelectionProtective Functions OC3Warranty Parts and Service Technical Services GE Fuji Drives USA, IncOut-of-Warranty Procedures MotorsIn-Warranty Failure Checklist Latest Fault Previous Faults No MessageFVR-C9S-2UX FVR-C9S-2UX FVR-C9S-2UX