F2 4 High Limiter F 2 5 Low Limiter
The upper and lower and lower limits of the output frequency can be set.
0Set as a percentage of the maximum frequency in increments of 1% within a range of 0 to 100%
1 0 0
If the value set for low limiter is higher than that set for the | 100% | High |
high limiter, the high limiter will take priority and the low |
| |
| limiter | |
limiter will be ignored. Thus, operation will always be in |
| |
|
| |
accordance with the high limiter value regardless of the |
|
|
frequency setting. | Output |
|
| frequency |
|
Low limiter
100%
Frequency setting
F 2 6 Bias Frequency
Outputs a bias frequency with respect to the analog frequency setting.
0Set as a percentage of the maximum frequency in increments of 1% within a range of 0 to 100%
1 0 0
F 2 7 THR Terminal Function
Bias
Frequency 100% setting
This function enables terminal THR to be used for two different functions by changing the data code as follows:
0External alarm input
1Multistep speed selection (X1)
This function data cannot be changed during operation. (Possible to change only in STOP mode).
F 2 8 BX Terminal Function
This function enables terminal BX to be used for two different functions by changing the data code as follows:
0Motor
1Multistep speed selection (X2)
This function data cannot be changed during operation. (Possible to change only in STOP mode).
32