GE FVR-C9S-2UX Drive Series instruction manual Terminal Function Explanation

Page 18

FVR-C9S-2UX

10. Terminal Function Explanation

Terminal Function Explanation

Classi-

Terminal Code

Terminal Name

Explanation of Function

fication

 

 

 

Main

L1, L2, L3

Commercial power supply input

For connection of 3-Phase 200 to 230V commercial power

Circuit

terminals

supply

 

 

 

 

 

 

U, V, W

Drive Output Terminals

For connection of a 3-Phase motor

 

 

 

 

 

E (G)

Drive Grounding Terminals

Grounding terminal of drive chassis (case). Be sure to ground

 

the drive to prevent electric shock or to lower noise

 

 

 

 

 

 

 

Frequency

13

Power Supply for Frequency

Used as a power supply for frequency setter (variable

Setting

Setting

resistor: 1 - 5K ohm) (DC + 10V, 10mA max)

 

 

 

 

 

 

12

Frequency Setting Voltage Input

DC 0 - +10V / 0 - 100% (Input resistance: 22K ohm)

 

 

 

 

 

11*

Frequency Setting Common

Common terminal for frequency setting signals 12 and 13

 

Terminal

 

 

 

 

 

 

 

Control

FWD

Forward/Stop Command Input

Forward-direction operation takes place when FWD-CM is

closed. Drive decelerates and stops when FWD-CM is

Input

Terminal

 

opened

 

 

 

 

 

 

 

 

REV

Reverse/Stop Command Input

Reverse-direction operation takes place when REV-CM is

 

Terminal

closed. Drive decelerates and stops when REV-CM is opened

 

 

 

 

 

 

 

BX

Motor Coast-to-Stop Input

•Drive output is cut off instantly and motor will coast-to-

 

Terminal

stop when BX-CM is closed. Alarm signal is not outputted.

 

 

 

 

 

•This functions as multistep frequency selection terminal X2

 

 

 

when changing function.

 

 

 

•When THR-CM is opened during operation, drive output is

 

THR

External Alarm Input Terminal

cut (motor will coast-to-stop) and an alarm signal is

 

 

 

outputted. This signal is latched and reset by RST input.

 

 

 

•This functions as multistep frequency selection terminal X1

 

 

 

when changing functions.

 

RST

Alarm Reset Terminal

When RST-CM is closed, the drive fault is reset.

 

 

 

 

 

CM*

Control Input Common Terminal

Common terminal for control input signals

 

 

 

 

 

 

 

C92-03

* Electric potential of 11 terminal is identical with that of CM terminal.

18

Image 18
Contents FVR-C9S-2UX Drive Series Product specifications are subject to change without notice Contents Safety Precautions Wiring Fire and Electric Shock HazardOperation Electric Shock Hazard Inspection Upon Receipt NameplatePart Names TypeSpecifications Input power Voltage/frequency Supply voltage 3%Type FVR C9S-2UX F12 F25 F50 External Dimensions DWG 1 FVRF12C9S-2UX to FVROO1C9S-2UXDWG 2 FVR002C9S to FVR003C9S-2UX FVR005C9S-2UX Installation Conditions Installation InstructionsWiring Mounting Direction and SpaceDisconnect CRG Lamp Basic Wiring Diagrams 30CKeypad Panel Operation External Signal Operation FABApplication of Wiring and Equipment Applicable motor output Hp Drive typeTerminal Function Explanation Terminal Function ExplanationTerminal Function Explanation Pre-Operation Inspection Frequency Setting MethodOperation Test Run Check PointsSelecting Operation Method RUN/STOPKeypad Panel Part Names and FunctionsControlling Method for Keypad Panel Function setting method Function Explanation Function Code TablesMotor Running Code 0 Data Protection 1 Frequency Command2 Operation Command 3 Maximum FrequencyElectronic Thermal Overload Relay Level Torque Boost8 Electronic Thermal Overload Relay Low High30% 1 Gain for Frequency Setting Signal 2 DC Brake3 DC Brake Braking Time 6 Fault Memory 4 Starting Frequency5 Motor Running Sound 8 Retry 9 Motor Characteristics7 Data Initialization Jump Frequency Range7 THR Terminal Function 4 High Limiter F 2 5 Low Limiter6 Bias Frequency 8 BX Terminal FunctionMultistep Speed Setting 1 Speed Multistep Speed Setting 2 SpeedMultistep Speed Setting 3 Speed 2 FM Terminal Output Level Calibration 3 FM Terminal Function SelectionProtective Functions OC3Out-of-Warranty Procedures Warranty Parts and ServiceTechnical Services GE Fuji Drives USA, Inc MotorsIn-Warranty Failure Checklist Latest Fault Previous Faults No MessageFVR-C9S-2UX FVR-C9S-2UX FVR-C9S-2UX