4. Specifications
Type (FVR _ _ _ |
|
| F12 |
| F25 | F50 | 001 |
| 002 |
| 003 |
| 005 |
| |
Applicable motor output1 |
| [Hp] | 1/8 |
| 1/4 | 1/2 | 1 |
| 2 |
| 3 |
| 5 |
| |
| Rated capacity2 |
| [kVA] | 0.28 |
| 0.56 | 1.0 | 1.6 |
| 2.8 |
| 4.0 |
| 6.6 |
|
| Voltage |
| [V] |
| |||||||||||
|
|
|
| to input voltage) |
|
|
|
|
|
|
|
|
| ||
Output Rating | Rated current |
| [A] | 0.7 |
| 1.4 | 2.5 | 4.0 |
| 7.0 |
| 10.0 |
| 16.5 |
|
| Overload current rating |
| 150% 1 min. |
|
|
|
|
|
|
|
|
| |||
| Rated frequency |
| [Hz] | 50/60 Hz |
|
|
|
|
|
|
|
|
|
| |
| Phase, voltage, frequency |
|
|
|
|
|
|
| |||||||
| Allowable variation in |
| Voltage: =10 - 15% Frequency: 15% (Imbalance in power |
|
| ||||||||||
Input power | voltage/frequency |
| supply voltage: 3%) |
|
|
|
|
|
|
|
| ||||
supply | Instantaneous voltage drop |
| Drive is kept running if voltage is 165V or more. If voltage drops |
| |||||||||||
| withstanding capacity |
| more than 165V from rated voltage, drive is run for 15ms.3 |
|
| ||||||||||
| Required power supply | [kVA] | 0.3 |
| 0.7 | 1.2 | 1.8 |
| 3.2 |
| 4.5 |
| 7.3 |
| |
| capacity |
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Adjustment | Max. freq.4 | [Hz] |
|
| ||||||||||
|
| Base freq. | [Hz] |
|
| ||||||||||
| Starting freq. | [Hz] |
|
|
|
| |||||||||
Output | Accuracy |
|
| Analog setting: ±1.0% of max. frequency (25±10°C) |
|
| |||||||||
frequency |
|
|
| Digital setting: ±0.01% of max. frequency |
|
| |||||||||
| Setting resolution |
| Analog setting:1/255 of max. frequency |
|
|
|
|
|
| ||||||
|
|
|
|
|
| (ex. 0.25 Hz / 60 Hz, 0.5 Hz / 120 Hz) |
|
|
|
| |||||
|
|
|
| Digital Setting: 0.1 Hz (99.9 Hz max) 1 Hz |
|
| |||||||||
| Control method |
|
| Sine wave PWM control |
|
|
|
|
|
|
|
| |||
|
|
|
| (Extremely low noise by high frequency carrier) |
|
|
|
| |||||||
Control | Operation |
|
| Keypad operation: Operation control by RUN/STOP keys |
|
| |||||||||
|
|
|
| Terminal strip: | Forward command. Reverse command. |
|
| ||||||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| External alarm. |
|
|
|
|
|
| ||
1) "Applicable motor" indicates a standard |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
2)"Rated capacity" indicates a capacity at 230V rating.
3)This applies to the case where momentary power failure occurs under such conditions that rated voltage is inputted and load factor is 85%.
4)Shows the case where an applicable motor equipped with an AC reactor (option) on the input side is used.
8