American Dryer Corp ADS-464 II manual Machine Main Power Shuts Down Blue Indicator Off

Page 50

3.Machine Main Power Shuts Down (“Blue” Indicator Off)

a.PROBABLE CAUSES;

1)Sprinkler activated.

2)OL12 (overload #12) tripped.

3)“UNDER VOLTAGE FEATURE” of main disconnect has tripped.

4)Sprinkler circuit defective.

b.POSSIBLE SOLUTIONS;

1)Check if the sprinkler is activated, is “SPRINKLER RESET” button lit? Is the sprinkler alarm horn “ON”? Does the sprinkler water valve have its “ON” indicator extended?

If yes, it indicates that the sprinkler circuit has shutdown the Main Disconnect, press the lit “SPRINKLER RESET” button, does it reset?

If “NO,” go to paragraph 2 below

2)Verify that OL12 (overload #12) has not tripped

If “YES,” check circuit, reset OL12, and test

If “NO,” go to paragraph 3 below

3)The main disconnect has an “UNDER VOLTAGE DROP OUT FEATURE.” This feature requires that 110 VAC be present to engage the disconnect switch. If 110 VAC is removed from Pin #51 and Pin #52 on the switch, the disconnect will drop out automatically. Verify that 110 volts AC is supplied to the disconnect and that wires are secure.

If 110 VAC is present, the disconnect may be defective

If 110 VAC is not present go to the beginning of section #3 at the top of the page.

4)Sprinkler circuit may be defective.

46

Image 50
Contents ADS-464 Installation/Operator’s Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Motors ServicePower Malfunctions Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Reattach The Control Pendant Arm Installation ProceduresReassembly of Dryer Reassembly Instructions For Dryers Shipped In Three 3 Pieces Page Location Requirements Internal AIR, ELECTRICAL, and Water Connections Air Front Tilt Piston and Sprinkler LinesPage Temperature Probe, Base, and Tumbler Basket Disconnects Electric Tumbler Basket MotorsPage Pendant Tumbler Basket Junction Box Disconnect Left Drum MotorExternal Supply Connections Condensate return line must be 1-1/4 pipe Exhaust Ducting Page Latest Edition Electrical RequirementsElectrical Requirements Electrical Service Specifications ADS-464 SteamPage Fresh AIR Supply Requirements Steam Information Steam RequirementsShut Down Instructions PRE START-UP Preparation for OperationSuggested Cleaning Schedule Routine MaintenanceCleaning Clean any lint accumulation from inside the heat consoleMonthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaimer Adjustment Remove Electricity from the Unit Compressed AIR System Page Safety Devices Door Open Parts SERVICE/PARTS InformationService Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Troubleshooting Troubleshooting Table of Contents NumberMain Disconnect Will Not Turn On Power MalfunctionsVerify red Sprinkler Power on main panel to be illuminated If NO, refer to paragraph #1 above Machine Main Power Shuts Down Blue Indicator Off Sprinkler circuit may be defective3CR CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page Emergency Stop E-Stop Buttons 1, 2, Malfunctioning PLC Programmable Logic ControllerPage PLC Message HI-TEMP Fault General DescriptionPage Page Tumbler Basket Section Electrical Malfunctions IntroductionDrum Rotation Sensor PRS1 Rear Panel Control Problems Emergency Stop E-Stop Function If YES, refer to section #3a If NO, refer to section #3b PLC OUT PIN 1 = Drum Reverse PLC OUT PIN 2 = Drum Forward PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP Wiring Back the PLC Programmable Logic Controller DS1-B=LOAD Door Switch DS2-B=UNLOAD Door SwitchProbable Solutions Base Section Electrical Malfunctions Lint Drawer Proximity Switches Wiring Back to the PLC Programmable Logic ControllerPage Probable Causes Load Level Unload Tumbler Reverse Tumbler Forward ADS-464 Pendant Assembly DiagramPendant Control Malfunctions SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Wiring Diagram Fuse 4 on Main Electrical Panel Faulty SwitchesWiring Back to PLC Programmable Logic Controller Another Emergency Stop E-Stop Button Temperature SensingDisconnect Plug Faulty Switch Wiring Back to TB1 Temperature Sensing Component Descriptions Exhaust RTD Resistive Temperature Device Sens1With the control voltage OFF Circuit Wiring to the Analog Input Module MotorsVerify current setting Check circuit Check motor Retest ADS-464 Idling ADS-464 Running ADC113074 1- 01/24/00-10