American Dryer Corp ADS-464 II manual ADS-464 Steam, Electrical Service Specifications

Page 27

2.Electrical Service Specifications

ADS-464 (Steam)

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.

B.Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3Ø dryer must be 3-pole type.

SERVICE

 

WIRE

APPROX.

MINIMUM

FUSING

CIRCUIT

PHASE

AMP DRAW

Dual Element

VOLTAGE

SERVICE

WIRE SIZE

BREAKER

 

60 Hz

50 Hz

Time Delay

 

 

 

 

 

208

3/4

112

112

1/0

150

150

 

 

 

 

 

 

 

 

240

3/4

107

108

1

150

150

 

 

 

 

 

 

 

 

380

3/4

---

63

4

100

100

 

 

 

 

 

 

 

 

416

3/4

---

60

4

90

100

 

 

 

 

 

 

 

 

460

3/4

53

---

4

80

90

 

 

 

 

 

 

 

 

DEDICATED SPRINKLER SERVICE

Dryer Nameplate

---

2

16

3.5

5

 

 

 

 

 

 

 

* AWG Stranded Type Wire ... for individual lengths less than 100 feet (31 m).

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the right side of the main electrical enclosure. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to the dryer components due to improper voltage will automatically VOID THE WARRANTY.

IMPORTANT: For proper sprinkler and dryer operation, sprinkler must be powered by a “separate or dedicated” single-phase (1ø) multi-wire branch circuit at dryer’s nameplate voltage.

NOTE: For 4-wire service, cap the neutral.

NOTE: Contact the factory for electrical information not listed.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or obligation.

23

Image 27
Contents ADS-464 Installation/Operator’s Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Service Power MalfunctionsMotors Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Installation Procedures Reassembly of DryerReattach The Control Pendant Arm Reassembly Instructions For Dryers Shipped In Three 3 Pieces Page Location Requirements Air Front Tilt Piston and Sprinkler Lines Internal AIR, ELECTRICAL, and Water ConnectionsPage Electric Tumbler Basket Motors Temperature Probe, Base, and Tumbler Basket DisconnectsPage Pendant Left Drum Motor Tumbler Basket Junction Box DisconnectExternal Supply Connections Condensate return line must be 1-1/4 pipe Exhaust Ducting Page Electrical Requirements Electrical RequirementsLatest Edition ADS-464 Steam Electrical Service SpecificationsPage Fresh AIR Supply Requirements Steam Requirements Steam InformationShut Down Instructions Preparation for Operation PRE START-UPClean any lint accumulation from inside the heat console Routine MaintenanceCleaning Suggested Cleaning ScheduleMonthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaimer Adjustment Remove Electricity from the Unit Compressed AIR System Page Safety Devices Door Open SERVICE/PARTS Information ServiceParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Troubleshooting Table of Contents Number TroubleshootingPower Malfunctions Verify red Sprinkler Power on main panel to be illuminatedMain Disconnect Will Not Turn On If NO, refer to paragraph #1 above Sprinkler circuit may be defective Machine Main Power Shuts Down Blue Indicator OffSprinkler Circuit Components 3CR CRB Not UsedSprinkler Circuit Description Page Malfunctioning PLC Programmable Logic Controller Emergency Stop E-Stop Buttons 1, 2,Page General Description PLC Message HI-TEMP FaultPage Page Introduction Tumbler Basket Section Electrical MalfunctionsDrum Rotation Sensor PRS1 Rear Panel Control Problems Emergency Stop E-Stop Function If YES, refer to section #3a If NO, refer to section #3b PLC OUT PIN 1 = Drum Reverse PLC OUT PIN 2 = Drum Forward PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Wiring Back the PLC Programmable Logic ControllerProbable Solutions Base Section Electrical Malfunctions Wiring Back to the PLC Programmable Logic Controller Lint Drawer Proximity SwitchesPage Probable Causes SEL a = Load SEL B = Unload ADS-464 Pendant Assembly DiagramPendant Control Malfunctions Load Level Unload Tumbler Reverse Tumbler ForwardTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Wiring Back to PLC Programmable Logic ControllerWiring Diagram Temperature Sensing Disconnect Plug Faulty Switch Wiring Back to TB1Another Emergency Stop E-Stop Button Exhaust RTD Resistive Temperature Device Sens1 Temperature Sensing Component DescriptionsWith the control voltage OFF Motors Circuit Wiring to the Analog Input ModuleVerify current setting Check circuit Check motor Retest ADS-464 Idling ADS-464 Running ADC113074 1- 01/24/00-10