4.Front PanelBLUE” Light and “RED” Light “ON” ADS-464 “ON” button does respond ...

a.PROBABLE CAUSES;

1)EMERGENCY STOP(E-Stop) BUTTONS 1, 2, and 3.

b.POSSIBLE SOLUTIONS;

1)Verify that ALLEMERGENCY STOP(E-Stop) buttons are pushed in.

EMERGENCY STOP 1 - main enclosed door

EMERGENCY STOP 2 - pendant control

EMERGENCY STOP 3 - rear control panel (2-door models only)

If ALLEMERGENCY STOP(E-Stop) buttons are “disengaged,” press “ON” located on the main enclosure door.

If “NO,” go to section #3 on page 46

Does the system “GREEN” “ON” light illuminate?

If not, check the “EMERGENCY STOP(E-Stop) and drying system “ON/OFF” circuits. (Refer to ladder diagram.)

5.Front PanelBLUE” (main panel) light, “RED” (sprinkler power) light, and “GREEN” (control power) light “ON

The system has one or more of the following symptoms;

• OPERATOR INTERFACE TERMINAL - no display or displays “LINE FAULT” message

• PROGRAMMABLE LOGIC CONTROLLER (PLC) - no indicator lights “ON”

• CONVENIENCE OUTLET - no power

HI-LIMIT CONTROLLERS (HLS1 and HLS2) - no display

a.PROBABLE CAUSES;

1)Fuse 7 -- PLC (Programmable Logic Controller) power Fuse 8 -- 24 volt DC power

Fuse 9 -- convenience outlet Fuse 10 - hi-limit controller power

2)Malfunctioning PLC (Programmable Logic Controller).

50

Image 54
Contents ADS-464 Installation/Operator’s Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Service Power MalfunctionsMotors Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Installation Procedures Reassembly of DryerReattach The Control Pendant Arm Reassembly Instructions For Dryers Shipped In Three 3 Pieces Page Location Requirements Internal AIR, ELECTRICAL, and Water Connections Air Front Tilt Piston and Sprinkler LinesPage Temperature Probe, Base, and Tumbler Basket Disconnects Electric Tumbler Basket MotorsPage Pendant Tumbler Basket Junction Box Disconnect Left Drum MotorExternal Supply Connections Condensate return line must be 1-1/4 pipe Exhaust Ducting Page Electrical Requirements Electrical RequirementsLatest Edition Electrical Service Specifications ADS-464 SteamPage Fresh AIR Supply Requirements Steam Information Steam RequirementsShut Down Instructions PRE START-UP Preparation for OperationSuggested Cleaning Schedule Routine MaintenanceCleaning Clean any lint accumulation from inside the heat consoleMonthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaimer Adjustment Remove Electricity from the Unit Compressed AIR System Page Safety Devices Door Open SERVICE/PARTS Information ServiceParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Troubleshooting Troubleshooting Table of Contents NumberPower Malfunctions Verify red Sprinkler Power on main panel to be illuminatedMain Disconnect Will Not Turn On If NO, refer to paragraph #1 above Machine Main Power Shuts Down Blue Indicator Off Sprinkler circuit may be defective 3CR CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page Emergency Stop E-Stop Buttons 1, 2, Malfunctioning PLC Programmable Logic ControllerPage PLC Message HI-TEMP Fault General DescriptionPage Page Tumbler Basket Section Electrical Malfunctions IntroductionDrum Rotation Sensor PRS1 Rear Panel Control Problems Emergency Stop E-Stop Function If YES, refer to section #3a If NO, refer to section #3b PLC OUT PIN 1 = Drum Reverse PLC OUT PIN 2 = Drum Forward PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP Wiring Back the PLC Programmable Logic Controller DS1-B=LOAD Door Switch DS2-B=UNLOAD Door SwitchProbable Solutions Base Section Electrical Malfunctions Lint Drawer Proximity Switches Wiring Back to the PLC Programmable Logic ControllerPage Probable Causes Load Level Unload Tumbler Reverse Tumbler Forward ADS-464 Pendant Assembly DiagramPendant Control Malfunctions SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Wiring Back to PLC Programmable Logic ControllerWiring Diagram Temperature Sensing Disconnect Plug Faulty Switch Wiring Back to TB1Another Emergency Stop E-Stop Button Temperature Sensing Component Descriptions Exhaust RTD Resistive Temperature Device Sens1With the control voltage OFF Circuit Wiring to the Analog Input Module MotorsVerify current setting Check circuit Check motor Retest ADS-464 Idling ADS-464 Running ADC113074 1- 01/24/00-10