•Check switch and actuator placement and tilt actuation.
NOTE: If actuator is at a 90º or greater angle with the base, actuator will be damaged if machine is lowered.
•If “NO,” check associated:
•Switch and Wiring
•Check wiring back to the base electrical junction box
•Check PLC (Programmable Logic Controller)
•Refer to the blueprints: Main Electrical Panel Diagram, Base Electrical Junction Box Wiring Diagram
•Retest; verify that the signal is operational
1b) Place the
•Actuate the Rear Down Switch by hand
•Have someone verify that PLC (Programmable Logic Controller) input L.E.D. (light emitting diode) #12 lights when the switch actuator is down, and is OFF when the actuator is up
•Does L.E.D. #12 come “ON” when the switch is down?
•If “YES,” wiring is okay
•Check switch, actuator placement and tilt actuation
NOTE: If actuator is at 90º or greater angle with the base, the actuator will be damaged if machine is lowered.
•If “NO,” check associated:
•Switch and wiring
•Check wiring back to the base electrical junction box
•Check PLC (Programmable Logic Controller)
•Refer to blueprints: Main Electrical Panel Diagram, Base Electrical Junction Box Wiring Diagram
•Retest; verify that the signal is operational
3.0Lint Screen Mechanism Problem “SCREEN FAULT”
A “SCREEN FAULT” message is generated by the incorrect state of the lint screen mechanism sensor switch. The following information will address the correct signal, since it is associated with the Base Electrical Junction Box.
65