American Dryer Corp ADS-464 II manual

Page 69

Check switch and actuator placement and tilt actuation.

NOTE: If actuator is at a 90º or greater angle with the base, actuator will be damaged if machine is lowered.

If “NO,” check associated:

Switch and Wiring

Check wiring back to the base electrical junction box

Check PLC (Programmable Logic Controller)

Refer to the blueprints: Main Electrical Panel Diagram, Base Electrical Junction Box Wiring Diagram

Retest; verify that the signal is operational

1b) Place the ADS-464 in the UNLOAD position; TILTED FORWARD

Actuate the Rear Down Switch by hand

Have someone verify that PLC (Programmable Logic Controller) input L.E.D. (light emitting diode) #12 lights when the switch actuator is down, and is OFF when the actuator is up

Does L.E.D. #12 come “ON” when the switch is down?

If “YES,” wiring is okay

Check switch, actuator placement and tilt actuation

NOTE: If actuator is at 90º or greater angle with the base, the actuator will be damaged if machine is lowered.

If “NO,” check associated:

Switch and wiring

Check wiring back to the base electrical junction box

Check PLC (Programmable Logic Controller)

Refer to blueprints: Main Electrical Panel Diagram, Base Electrical Junction Box Wiring Diagram

Retest; verify that the signal is operational

3.0Lint Screen Mechanism Problem “SCREEN FAULT”

A “SCREEN FAULT” message is generated by the incorrect state of the lint screen mechanism sensor switch. The following information will address the correct signal, since it is associated with the Base Electrical Junction Box.

65

Image 69
Contents ADS-464 Installation/Operator’s Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Service Power MalfunctionsMotors Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Installation Procedures Reassembly of DryerReattach The Control Pendant Arm Reassembly Instructions For Dryers Shipped In Three 3 Pieces Page Location Requirements Air Front Tilt Piston and Sprinkler Lines Internal AIR, ELECTRICAL, and Water ConnectionsPage Electric Tumbler Basket Motors Temperature Probe, Base, and Tumbler Basket DisconnectsPage Pendant Left Drum Motor Tumbler Basket Junction Box DisconnectExternal Supply Connections Condensate return line must be 1-1/4 pipe Exhaust Ducting Page Electrical Requirements Electrical RequirementsLatest Edition ADS-464 Steam Electrical Service SpecificationsPage Fresh AIR Supply Requirements Steam Requirements Steam InformationShut Down Instructions Preparation for Operation PRE START-UPCleaning Routine MaintenanceSuggested Cleaning Schedule Clean any lint accumulation from inside the heat consoleMonthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaimer Adjustment Remove Electricity from the Unit Compressed AIR System Page Safety Devices Door Open SERVICE/PARTS Information ServiceParts Returning Warranty Cards Warranty InformationWarranty Returning Warranty PartsPage Troubleshooting Table of Contents Number TroubleshootingPower Malfunctions Verify red Sprinkler Power on main panel to be illuminatedMain Disconnect Will Not Turn On If NO, refer to paragraph #1 above Sprinkler circuit may be defective Machine Main Power Shuts Down Blue Indicator OffSprinkler Circuit Components 3CR CRB Not UsedSprinkler Circuit Description Page Malfunctioning PLC Programmable Logic Controller Emergency Stop E-Stop Buttons 1, 2,Page General Description PLC Message HI-TEMP FaultPage Page Introduction Tumbler Basket Section Electrical MalfunctionsDrum Rotation Sensor PRS1 Rear Panel Control Problems Emergency Stop E-Stop Function If YES, refer to section #3a If NO, refer to section #3b PLC OUT PIN 1 = Drum Reverse PLC OUT PIN 2 = Drum Forward PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Wiring Back the PLC Programmable Logic Controller Probable Solutions Base Section Electrical Malfunctions Wiring Back to the PLC Programmable Logic Controller Lint Drawer Proximity SwitchesPage Probable Causes Pendant Control Malfunctions ADS-464 Pendant Assembly DiagramLoad Level Unload Tumbler Reverse Tumbler Forward SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Wiring Back to PLC Programmable Logic ControllerWiring Diagram Temperature Sensing Disconnect Plug Faulty Switch Wiring Back to TB1Another Emergency Stop E-Stop Button Exhaust RTD Resistive Temperature Device Sens1 Temperature Sensing Component DescriptionsWith the control voltage OFF Motors Circuit Wiring to the Analog Input ModuleVerify current setting Check circuit Check motor Retest ADS-464 Idling ADS-464 Running ADC113074 1- 01/24/00-10