Relay PCA 04523 | Addendum to |
Input Gain Selector | Output Scale Selector | Type J Compensation | Type J Compensation | Termination Selector | Input Gain Selector |
1 – 11 | 2 – 12 | 3 – 13 | 4 – 14 | 5 – 15 | 6 – 16 |
|
|
|
|
|
|
Output Scale Selector 7 – 17
Type J Compensation 8 – 18
Type J Compensation 9 – 19
Termination Selector 10 – 20
TC1
TC2
Figure 2-8: Thermocouple Configuration Jumper (JP5) Pin-Outs
Table
TC | TERMINATION | OUTPUT | JUMPER |
| JUMPER | |
SCALE | BETWEE | USED ON | ||||
TYPE | TYPE | COLOR | ||||
TYPE | N PINS |
| ||||
|
|
|
| |||
|
|
|
|
|
|
INPUT TC1 (J15)
K | GROUNDED | 5mV / °C | 2 – 12 | M100EH with Mini HiCon Converter | BROWN |
|
|
| 4 – 14 |
|
|
|
|
|
|
|
|
K |
|
| 2 – 12 |
|
|
ISOLATED | 5mV / °C | 4 – 14 | M100EH with Mini HiCon Converter | GREY | |
|
|
| 5 – 15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
K | ISOLATED | 10mV / °C | 4 – 14 | M100E/M200E with Moly Converter | PURPLE |
|
|
| 5 – 15 |
|
|
|
|
|
|
|
|
J |
|
| 1 – 11 |
|
|
ISOLATED | 10mV / °C | 3 – 13 | M100E/M200E with Moly Converter | RED | |
|
|
| 5 – 15 |
|
|
|
|
|
|
|
|
J | GROUNDED | 10mV / °C | 1 – 11 | M100E/M200E with Moly Converter | GREEN |
|
|
| 3 – 13 |
|
|
05118 Rev B3 | 13 |