Remote Operation

SCPI Commands for Digital Interfaces

Configure

Other

Protection

Mechanisms

Fold Protection

Fold protection causes the supply to shut down if the selected regulation mode is entered. A delay time may be specified as well.

To set the fold mode:

OUTP:PROT:FOLD {CCCVCPNONE}

Where:

NONE indicates fold protection is disabled.

CCindicates the supply will shut down due to constant current condition. CV indicates the supply will shut down due to constant voltage.

CP indicates the supply will shut down due to constant power. The default value is NONE.

To set the fold delay:

OUTP:PROT:FOLD:DEL <delay_time>

Where:

<delay_time> is a value in the range of 0–60 seconds.

Units may be specified as “ms” (milliseconds) “s” (seconds), or “min” (minutes). If no units are specified, the default seconds are assumed. (Increments of 0.1s are allowed.) The default value is 0.5 second.

132

Operating Manual for XDC Series Power Supply