Installation

Load Connections

Multiple

Loads

To connect multiple loads in parallel:

Follow the “Single Load” procedure with the following exception:

To minimize interaction between loads, bring the wiring for each load directly back to the supply output. When each load to the power supply is wired separately, the loads will see only the precisely regulated output from the supply. If 2 loads share a single cable, the fluctuation in current to one load will cause the voltage to vary on the others. This is due to wire impedance drops.

Figure 2.7 Fastening the Output Wires (6000 Watt)

(Low and Medium Voltage)

52

Operating Manual for XDC Series Power Supply

Page 54