Specifications and Characteristics

Electrical Specifications—Summary

Table E.3Specifications for 6000 Watt units (80V to 600V Models)

Models

80–75

100–60

150–40

300–20

600–10

Output Ratings:

 

 

 

 

 

Output Voltage 1

0–80 V

0–100 V

0–150 V

0–300 V

0–600 V

Output Current 2

0–75 A

0–60 A

0–40 A

0–20 A

0–10 A

Output Power

6000 W

6000 W

6000 W

6000 W

6000 W

Line Regulation: 3

 

 

 

 

 

Voltage (0.01% of Vmax)

8 mV

10 mV

15 mV

30 mV

60 mV

Current (0.05% of Imax)

37.5 mA

30 mA

20 mA

10 mA

5 mA

Load Regulation: 4

 

 

 

 

 

Voltage (0.05% of Vmax + 5 mV)

45 mV

55 mV

80 mV

155 mV

305 mV

Current (0.1% of Imax + 20 mA)

95 mA

80 mA

60 mA

40 mA

30 mA

Meter Accuracy:

 

 

 

 

 

Voltage (0.15% of Vmax)

120 mV

150 mV

225 mV

450 mV

900 mV

Current (0.5% of Imax)

375 mA

300 mA

200 mA

100 mA

50 mA

Output Noise (0–20 MHz):

 

 

 

 

 

Voltage (p–p)

100 mV

100 mV

150 mV

250 mV

350 mV

Output Ripple (rms):

 

 

 

 

 

Voltage

15 mV

20 mV

20 mV

30 mV

80 mV

Current 5

320 mA

230 mA

120 mA

50 mA

25 mA

OVP Adjustment Range:

 

 

 

 

 

(0% to 110% of Vmax)

0–88 V

0–110 V

0–165 V

0–330 V

0–660 V

 

 

 

 

 

 

Efficiency: 6

0.89

0.90

0.90

0.91

0.91

1.Minimum output voltage is <0.3% of rated voltage at zero output setting.

2.Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.

3.For input voltage variation over the AC input voltage range, with constant rated load.

4.For 0–100% load variation, with constant nominal line voltage.

5.Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.

6.Typical efficiency at nominal input voltage and full output power.

230