Specifications and Characteristics

AC Line Input Specifications

AC Line Input Specifications

The input to the power supply requires the following specifications.

AC Line Input

Voltage

Operating

Ranges

Table E.9AC Line Input Specifications

Operating Range

 

 

 

nominal 208Vrms (Standard)

190 to 242 Vac 3 φ (3 wire + safety

nominal 400Vrms (with HV-Input option)

ground)

 

 

342 to 500 Vac 3 φ (3 wire + safety

 

 

ground)

Frequency Range

 

47 to 63 Hz

 

 

 

Maximum Peak In-rush Current at turn on

35

Arms (6000 Watt)

 

 

70

Arms (12000 Watt)

Minimum Power Factor1

 

 

nominal 208Vrms (Standard)

0.95

nominal 400Vrms (with HV-Input option)

0.9

 

Operating Current

(Standard)

 

 

nominal 208V

 

 

Maximum2 rms

24

A (6000 Watt)

Typical3

 

48

A (12000 Watt)

 

20

A (6000 Watt)

 

 

40

A (12000 Watt)

 

 

 

 

Operating Current

(with HV-Input option)

 

 

nominal 400V

 

 

Maximum4 rms

13

A (6000 Watt)

Typical5

 

26

A (12000 Watt)

 

11 A (6000 Watt)

 

 

22

A (12000 Watt)

1.At nominal input voltage and maximum power

2.At 190Vac input voltage, 55°C ambient temperature and maximum power

3.At 208Vac input voltage, 25°C ambient temperature and maximum power

4.At 342Vac input voltage, 50°C ambient temperature and maximum power

5.At 400Vac input voltage, 25°C ambient temperature and maximum power