Specifications and Characteristics

Electrical Specifications—Summary

Table E.6Drift Specifications for 12000 Watt units (10V to 60V Models)

Models

10–1200

20–600

30–400

40–300

60–200

Drift (30 minutes): 1

 

 

 

 

 

Voltage (0.04% of Vmax)

4 mV

8 mV

12 mV

16 mV

24 mV

Current (0.6% of Imax)

7200 mA

3600 mA

2400 mA

1800 mA

1200 mA

Drift (8 hours): 2

 

 

 

 

 

Voltage (0.02% of Vmax)

2 mV

4 mV

6 mV

8 mV

12 mV

Current (0.05% of Imax)

600 mA

300 mA

200 mA

150 mA

100 mA

Temperature Coefficient: 3

 

 

 

 

 

Voltage (0.04% of Vmax/°C)

4 mV

8 mV

12 mV

16 mV

24 mV

Current (0.06% of Imax/°C)

720 mA

360 mA

240 mA

180 mA

120 mA

1.Maximum drift over 30 minutes with constant line, load, and temperature, after power on.

2.Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.

3.Change in output per °C change in ambient temperature, with constant line and load.

Release 3.0

233

Page 235
Image 235
Xantrex Technology XDC manual 233