Operation

Power Supply Operation

To set the current limits:

Step #

Do This

You Will See

1

MENU

ERROR MSGS

 

 

 

 

 

2

until you see the “SETPT

SETPT LIMIT

 

LIMIT” option

 

3

ENTER

Voltage Limit

 

 

 

 

 

4

 

Current Limit

5

ENTER

High 0A

 

 

 

 

 

6

Use the Current knob, arrow keys, or

High #####A

 

numeric keypad to enter a value. The

 

 

value must be within 0A to 103% of

 

 

the unit’s rated current.

 

 

 

 

7

ENTER

Low 0A

 

 

 

 

The Maximum setting is saved and

 

 

the Minimum setting appears.

8

Use the Voltage knob, arrow keys, or

Low #####A

 

numeric keypad to enter a value. The

 

 

value must be within 0A to 103% of

 

 

the unit’s rated current.

 

 

 

 

9

ENTER

The setting is saved and the display

returns to its default operating mode.

 

 