Specifications and Characteristics

Electrical Specifications—Summary

Table E.5Specifications for 12000 Watt units (10V to 60V Models)

Models

10-1200

20-600

30-400

40-300

60-200

Output Ratings:

 

 

 

 

 

Output Voltage 1

0–10 V

0–20 V

0–30 V

0–40 V

0–60 V

Output Current 2

0–1200 A

0–600 A

0–400 A

0–300 A

0–200 A

Output Power

12000 W

12000 W

12000 W

12000 W

12000 W

Line Regulation: 3

 

 

 

 

 

Voltage (0.01% of Vmax)

1 mV

2 mV

3 mV

4 mV

6 mV

Current (0.1% of Imax)

1200 mA

600 mA

400 mA

300 mA

200 mA

Load Regulation: 4

 

 

 

 

 

Voltage (0.05% of Vmax + 5 mV)

10 mV

15 mV

20 mV

25 mV

35 mV

Current (0.2% of Imax + 40 mA)

2440 mA

1240 mA

840 mA

640 mA

440 mA

Meter Accuracy:

 

 

 

 

 

Voltage (0.15% of Vmax)

15 mV

30 mV

45 mV

60 mV

90 mV

Current (0.5% of Imax)

6 A

3 A

2.0 A

1.5 A

1 A

Output Noise (0–20 MHz):

 

 

 

 

 

Voltage (p–p)

75 mV

75 mV

75 mV

75 mV

100 mV

Output Ripple (rms):

 

 

 

 

 

Voltage

10 mV

10 mV

12 mV

15 mV

15 mV

Current 5

6200 mA

3200 mA

2000 mA

1500 mA

900 mA

OVP Adjustment Range:

 

 

 

 

 

(0% to 103% of Vmax)

0–10.3 V

0–20.6 V

0–30.9 V

0–41.2 V

0–61.8 V

Efficiency: 6

0.85

0.87

0.87

0.87

0.89

1.Minimum output voltage is <0.3% of rated voltage at zero output setting.

2.Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.

3.For input voltage variation over the AC input voltage range, with constant rated load.

4.For 0–100% load variation, with constant nominal line voltage.

5.Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.

6.Typical efficiency at nominal input voltage and full output power.

232

Operating Manual for XDC Series Power Supply

Page 234
Image 234
Xantrex Technology XDC manual Models 10-1200 20-600 30-400 40-300 60-200