Specifications and Characteristics

Electrical Specifications—Summary

Table E.2Drift Specifications for 6000 Watt units (10V to 60V Models)

Models

10–600

20–300

30–200

40–150

60–100

Drift (30 minutes): 1

 

 

 

 

 

Voltage (0.04% of Vmax)

4 mV

8 mV

12 mV

16 mV

24 mV

Current (0.6% of Imax)

3600 mA

1800 mA

1200 mA

900 mA

600 mA

Drift (8 hours): 2

 

 

 

 

 

Voltage (0.02% of Vmax)

2 mV

4 mV

6 mV

8 mV

12 mV

Current (0.04% of Imax)

240 mA

120 mA

80 mA

60 mA

40 mA

Temperature Coefficient: 3

 

 

 

 

 

Voltage (0.04% of Vmax/°C)

4 mV

8 mV

12 mV

16 mV

24 mV

Current (0.06% of Imax/°C)

360 mA

180 mA

120 mA

90 mA

60 mA

1.Maximum drift over 30 minutes with constant line, load, and temperature, after power on.

2.Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.

3.Change in output per °C change in ambient temperature, with constant line and load.

Release 3.0