Xantrex Technology XDC manual Remote Interface Calibration Procedure

Models: XDC

1 254
Download 254 pages 27.31 Kb
Page 189
Image 189

Analog

Programming

Interface

0-10V Range

Calibration

Remote Interface Calibration Procedure

The 0-10V range of the analog programming interface must be calibrated separately. Follow the procedure exactly as for calibrating the 0-5V range, using the corresponding 10V menu options. All the analog signals will be scaled by a factor of 2.

Remote Interface Calibration Procedure

Calibration can also be done via front panel. See “Front Panel Calibration Procedure” on page 183.

Output Voltage

Calibration of voltage programming and readback are combined in a single procedure.

1.Set the load to open circuit. Attach a DVM across the output terminals.

2.Minimum calibration level

Set the output voltage to 10% by sending the command:

CAL:OUTP:VOLT:LEV MIN

3.Enter voltage data

Enter the voltage read from the external DVM. CAL:OUTP:VOLT:DATA <voltage>

4.Maximum calibration level

Set the output voltage to 90% by sending the command:

CAL:OUTP:VOLT:LEV MAX

5.Enter voltage data

Enter the voltage read from the external DVM. CAL:OUTP:VOLT:DATA <voltage>

6.Power supply calculates and stores calibration constants.

Output 1. Set the power supply and load operate at full output. You must ensure the power

Current supply is operating in current mode during current calibration. Place a shunt on the load line so that you can measure the current. Attach a DVM across the shunt

2.Minimum calibration level

Set the output current to 10% by sending the command:

CAL:OUTP:CURR:LEV MIN

Release 3.0

187

Page 189
Image 189
Xantrex Technology XDC manual Remote Interface Calibration Procedure, Analog Programming Interface 10V Range