Remote Operation

Remote Analog Operation

Table 4.3 Analog Pin Connections for Power Loop Back

Programming Line Pin #

 

User Line Pin #

B1

to

A7

 

 

 

B2

to

A6

 

 

 

Remote Interlock Using a Contact Closure

The interlock input may be configured for use with an external voltage free contact. Connect pins as shown:

Table 4.4 Analog Pin Connections with a Contact Closure

Programming Line Pin #

 

User Line Pin #

B2

to

A4

 

 

 

B1

to

A5

 

 

 

Closing an external contact across the interlock pins A4/A5 will then enable the unit. Opening the contact will disable the supply output.

Configure You may configure the analog programming lines to work in either a 0 to 5V range Analog or a 0 to10V range. You may also select whether the voltage, current or both are Control controlled with the programming lines. If you select only voltage or only current, the

other will be controlled via the front panel.

Front Panel

First, configure the analog programming lines.

Step #

Do This

You Will See

1

MENU

ERROR MSGS

 

 

 

 

 

2

5 times1

REMOTE CONFIG

3

ENTER

RS-232 Cfg

 

 

 

 

 

4

 

Analog Cfg

5

ENTER

Input 0-5V

 

 

 

 

6

or

0-5V or

0-10V

 

Select the input range.

 

 

 

 

 

7

ENTER

Setting is saved and menu is exited.

 

1. You can also press MENU 5 times.