Operation

Power Supply Operation

To set the Under-Current Protection:

Step #

Do This

You Will See

1

PROT SET

OVP SET 0V

ALARMS

2

PROT SET

ALARMS

Press repeatedly until the

UCP SET 0A

desired setting appears.

 

3

ENTER

UCP SET 0A

 

 

 

 

 

4

Use the Current knob, the numeric

UCP SET ####A

keypad, or the arrow keys to enter a

 

value. The value must be between

 

 

0–103% of the unit’s rated current.

 

5

ENTER

S/D if trip? N

 

 

 

 

 

6

Use the arrow keys to select Yes or No.

S/D if trip? Y

For this example, Yes is selected.

7

ENTER

This setting is saved and the display

 

 

returns to its default operating mode.

To set the Over-Power Protection:

Step #

Do This

You Will See

1

PROT SET

OVP SET 0V

ALARMS

2

PROT SET

ALARMS

Press repeatedly until the

OPP SET 0W

desired setting appears.

 

3

ENTER

OPP SET 0W

 

 

 

 

 

4

Use both the Current and Voltage

OPP SET ####W

knobs, or the numeric keypad, or the

 

arrow keys to enter a value. The

 

 

value must be between 0W and

 

 

103% of the unit’s rated power.

 

5

ENTER

S/D if trip? N

 

 

 

 

 

6

Use the arrow keys to select Yes or

S/D if trip? Y

 

No. For this example, Yes is selected.

 

7

ENTER

This setting is saved and the display

 

 

returns to its default operating mode.

Release 3.0

69