Chromalox CN2110 manual Sensor Input Wiring, Three-Wire RTD Inputs, Two-Wire RTD Inputs

Page 13

CN 2110 Temperature Controller

Sensor Input Wiring

continued

Three-Wire RTD Inputs

IMPORTANT: When making the three-wire RTD input connection, make the resistance of all three extension leadwires equal by using the same gauge and same length of wire for optimum accuracy. A three-wire RTD will generally have two wires of the same color. Connect the same colored wires to the RTDL connections. Connect the alternate colored wire to the RTDH connection.

Make three-wire RTD connections to terminals as shown in Figure 3.7.

RTDH

RTDL

RTDL

Shield Ground

Figure 3.7

Three-Wire RTD Connections with Shield

Two-Wire RTD Inputs

If using a two-wire RTD input, use heavier gauge leadwires to reduce leadwire resistance. Any leadwire resistance adds directly to sensor resistance, thus adding error to the process temperature measurement. It is also necessary to jumper the two RTDL terminals on the instrument to complete a two-wire hookup.

RTDH

RTDL

RTDL

Figure 3.8

Two-Wire RTD Connections

Section 3–Installation and Wiring

9

CN 2110

Image 13
Contents User’s Guide Omega.com Table of Contents CN 2110 Temperature ControllerPage Setting the Sensor and Control Mode Quick SetupAdjusting the Set Point Inspection and Unpacking IntroductionModel Identification Sensor and Control Type Selection Switches Installation and WiringRemoving Mounting Collars MountingController will now be held firmly in place Mount the CNGood Wiring Practices Thermocouple Inputs Sensor Input Wiring Sensor Wiring NotesThree-Wire RTD Inputs Sensor Input WiringTwo-Wire RTD Inputs R20 20 Amp Relay Output Wiring Control Output WiringDC Solid State Relay Drive, 24Vdc, 40mA Output Wiring Instrument Power Wiring Adjusting the Set Point Adjusting Set Point and ConfigurationConfiguration 5Move to .6until SP is next menu Displayed Exit ConfigurationSecurity Codes and Levels Configuration MenusOFF Control Operation Alarm Operation optional Control and Alarm OperationTuning PI Control Replacing Output Modules Module InstallationModule Option Descriptions RemovalAuto Cycle Time ReplacementTo reestablish the factory default values Calibration Offset Factory Default RecoveryCalibration Calibration Notes Calibration Factory Calibration RecoverySensor Calibration Control Adjustments SpecificationsSymptom Probable Cause Correction Steps TroubleshootingFAn FAIL, CN TroubleshootingPage Page Page USAWARRANTY/DISCLAIMER Temperature