Chromalox CN2110 manual Off

Page 19

CN 2110 Temperature Controller

Configuration Menus

continued

Menu

Adjustable

Factory

Security

Code Function

Range

Default

Level

 

 

 

 

Cycle Time

.1 to 60.0 Sec.

Output R1,

B

The time for the output to

 

R20 = 30

 

complete ON to OFF to ON

 

sec.

 

cycle. Used only with

 

T1, T5, T10

 

proportional control. A fast

 

 

cycle time provides better

 

DC = 1 sec.

 

control, but can cause

 

 

 

premature wear to contactor or

 

 

 

other power switching devices.

 

 

 

Magnetic contactors should not

 

 

 

be switched at less than a 30

 

 

 

second cycle time. This menu is

 

 

 

active when the dip switch is

 

 

 

set to “PI”.

 

 

 

On/Off Dead Band

1 to 100 °F or °C

5 Foc

B

The range above/below set point in which no control action takes place. Determines at what temperature the output switches ON and OFF. For a 5°F dead band, 2.5°F is above and below the set point. This menu is active when the dip switch is set to “ONOF”.

Alarm Type

Off, Hi or Lo

OFF

B

Select high or low alarm.

 

 

 

 

Alarm Set Point

Sensor Range

Span High

B

Temperature level that will

F or

C

 

 

°

°

 

 

actuate the alarm.

 

 

 

 

Alarm Dead Band

0 to 100 °F or °C

5

B

Difference of temperature from

 

 

 

 

alarm set point before an active

 

 

 

 

alarm resets.

 

 

 

 

Set Point Lower Limit

Sensor Range

Span Low

B

Lower limit to which set point

F or

C

 

 

°

°

 

 

may be set without security code access.

Set Point Upper Limit

Upper limit to which set point may be set without security code access. This prevents an operator from setting the set point temperature to a level which would damage equipment or process.

Sensor Range

Span High

B

°F or °C

 

 

Output Limit

0 to 100%

100

B

Limits the percentage of output that can be applied in proportional control.

For calibration menus (CoFF, dFLt, & CALS), see Section 7–Calibration

Section 4–Adjusting Set Point and Configuration

15

CN 2110

Image 19
Contents User’s Guide Omega.com Table of Contents CN 2110 Temperature ControllerPage Setting the Sensor and Control Mode Quick SetupAdjusting the Set Point Inspection and Unpacking IntroductionModel Identification Sensor and Control Type Selection Switches Installation and WiringRemoving Mounting Collars MountingController will now be held firmly in place Mount the CNGood Wiring Practices Thermocouple Inputs Sensor Input Wiring Sensor Wiring NotesThree-Wire RTD Inputs Sensor Input WiringTwo-Wire RTD Inputs R20 20 Amp Relay Output Wiring Control Output WiringDC Solid State Relay Drive, 24Vdc, 40mA Output Wiring Instrument Power Wiring Adjusting the Set Point Adjusting Set Point and ConfigurationConfiguration 5Move to .6until SP is next menu Displayed Exit ConfigurationSecurity Codes and Levels Configuration MenusOFF Control Operation Alarm Operation optional Control and Alarm OperationTuning PI Control Removal Module InstallationReplacing Output Modules Module Option DescriptionsAuto Cycle Time ReplacementTo reestablish the factory default values Calibration Offset Factory Default RecoveryCalibration Calibration Notes Calibration Factory Calibration RecoverySensor Calibration Control Adjustments SpecificationsSymptom Probable Cause Correction Steps TroubleshootingFAn FAIL, CN TroubleshootingPage Page Page USAWARRANTY/DISCLAIMER Temperature