Chromalox CN2110 manual Good Wiring Practices

Page 11

CN 2110 Temperature Controller

Good Wiring Practices

!

Separate wire into bundles—When planning the system wiring, separate wiring into functionally similar bundles, e.g.

Power leads

Sensor leads (if power leads must cross sensor leads, they should cross at a 90° angle)

Output signal lines

Separate sources of electrical noise—Locate all sources of electrical noise in your system, and separate these sources from the control system, e.g.

Motors

Contacts

Solenoids

Electrical noise can affect the function of any control system. When driving a contactor coil or other inductive load, an appropriate rated AC snubber circuit is recommended (Omega Part No. CNQUENCHARC).

Connect before power is applied—Make all electrical wiring connec- tions to the back of the controller before power is applied to the unit.

Comply with regulations—WARNING: All wiring practices must comply with local regulations. Failure to do so could result in damage to controller and/or personal injury or death from electrical shock.

This instrument is intended for panel mounting and the terminals must be enclosed within a panel. Use National Electric Code (NEC) Class 1 wiring for all terminals except the sensor terminals.

Check wiring decal—Check the wiring decal on the side of the unit to verify the model number. The wiring decal shows the wiring termina- tions. All wiring will be connected to the terminals on the back of the instrument case. Specific wiring instructions for different input and output types are given in this section. See also Figure 3.5.

Additional information—For sensor wiring practices, see “Sensor Input Wiring”. For additional information on good wiring practice, request IEEE Standard No. 518-1982 from IEEE, 345 East 47th St., New York, NY 10017 or www.ieee.org.

Sensor Input

Alarm Wiring

Wiring

COM NO NC

 

Output

Instrument

Wiring

Power Wiring

(T5, T10)

 

Figure 3.5

Output Wiring

(R1, R20, DC, or T1)

Wiring Terminal Identification

 

Section 3–Installation and Wiring

7

CN 2110

Image 11
Contents User’s Guide Omega.com Table of Contents CN 2110 Temperature ControllerPage Adjusting the Set Point Quick SetupSetting the Sensor and Control Mode Inspection and Unpacking IntroductionModel Identification Sensor and Control Type Selection Switches Installation and WiringRemoving Mounting Collars MountingController will now be held firmly in place Mount the CNGood Wiring Practices Thermocouple Inputs Sensor Input Wiring Sensor Wiring NotesTwo-Wire RTD Inputs Sensor Input WiringThree-Wire RTD Inputs DC Solid State Relay Drive, 24Vdc, 40mA Output Wiring Control Output WiringR20 20 Amp Relay Output Wiring Instrument Power Wiring Configuration Adjusting Set Point and ConfigurationAdjusting the Set Point 5Move to .6until SP is next menu Displayed Exit ConfigurationSecurity Codes and Levels Configuration MenusOFF Tuning PI Control Control and Alarm OperationControl Operation Alarm Operation optional Removal Module InstallationReplacing Output Modules Module Option DescriptionsAuto Cycle Time ReplacementCalibration Calibration Offset Factory Default RecoveryTo reestablish the factory default values Sensor Calibration Calibration Factory Calibration RecoveryCalibration Notes Control Adjustments SpecificationsSymptom Probable Cause Correction Steps TroubleshootingFAn FAIL, CN TroubleshootingPage Page Page USAWARRANTY/DISCLAIMER Temperature