Chromalox CN2110 manual Troubleshooting, Symptom Probable Cause Correction Steps

Page 26

Omega

Section 9—Troubleshooting

The following Troubleshooting Guide offers simple solutions to com- mon problems and explains the CN 2110’s Error Messages. Review this section for a possible solution to your problem before contacting Omega.

Note: For each symptom, perform correction steps in the order listed.

 

Symptom

Probable Cause

Correction Steps

 

 

 

 

 

 

 

 

 

Power applied, display

1.

No power applied

1.

Check power wiring

 

does not light, and

2.

External fuse open

 

and fusing

 

controller does not

 

 

 

 

 

 

2.

Power down and

 

function

 

 

 

 

 

 

repower up

 

 

 

 

 

 

 

 

 

 

 

 

 

Display alternates

1.

Open sensor

1.

Check sensor wiring

 

between HI and

2.

Out of calibration

2.

Check selection

 

SENS, CN 2110

 

 

 

 

switches

 

disables control

 

 

 

 

 

 

3. To verify that controller

 

output

 

 

 

 

 

 

is at fault, remove the

 

 

 

 

 

 

 

 

 

 

thermocouple and place

 

 

 

 

 

a jumper across the

 

 

 

 

 

sensor terminals of the

 

 

 

 

 

CN 2110. If the display

 

 

 

 

 

reads approximately

 

 

 

 

 

ambient, then the

 

 

 

 

 

sensor is open. Replace

 

 

 

 

 

the thermocouple.

 

 

 

 

4.

See Section 7–Calibra-

 

 

 

 

 

tion

 

 

 

 

 

 

 

 

Process does not

1.

No power being

1.

Verify Load LED is ON

 

heat up

 

applied to the load

2. Verify the heater or fuse

 

 

 

 

 

 

2.

Load fuse open

 

is not open

 

 

 

 

3. Verify output limit is set

 

 

 

 

 

to 100%

 

 

 

 

4. Verify set point is

 

 

 

 

 

greater than process

 

 

 

 

 

temperature

 

 

 

 

5.

Verify output wiring

 

 

 

 

 

 

 

 

Erratic operation

1.

Intermittent sensor

1.

Check sensor wiring or

 

 

 

connections

 

substitute sensor

 

 

2.

Controller failure

 

simulator

 

 

 

 

 

 

 

 

(internal electronics)

2.

Power down and

 

 

3.

External electrical

 

repower up

 

 

 

 

 

 

 

 

noise

3.

Contact Omega

CN 2110

22

Section 9–Troubleshooting

Image 26
Contents User’s Guide Omega.com CN 2110 Temperature Controller Table of ContentsPage Adjusting the Set Point Quick SetupSetting the Sensor and Control Mode Introduction Inspection and UnpackingModel Identification Installation and Wiring Sensor and Control Type Selection SwitchesMounting Removing Mounting CollarsMount the CN Controller will now be held firmly in placeGood Wiring Practices Sensor Input Wiring Sensor Wiring Notes Thermocouple InputsTwo-Wire RTD Inputs Sensor Input WiringThree-Wire RTD Inputs DC Solid State Relay Drive, 24Vdc, 40mA Output Wiring Control Output WiringR20 20 Amp Relay Output Wiring Instrument Power Wiring Configuration Adjusting Set Point and ConfigurationAdjusting the Set Point Exit Configuration 5Move to .6until SP is next menu DisplayedConfiguration Menus Security Codes and LevelsOFF Tuning PI Control Control and Alarm OperationControl Operation Alarm Operation optional Module Option Descriptions Module InstallationReplacing Output Modules RemovalReplacement Auto Cycle TimeCalibration Calibration Offset Factory Default RecoveryTo reestablish the factory default values Sensor Calibration Calibration Factory Calibration RecoveryCalibration Notes Specifications Control AdjustmentsTroubleshooting Symptom Probable Cause Correction StepsTroubleshooting FAn FAIL, CNPage Page Page USAWARRANTY/DISCLAIMER Temperature