Security Codes and Levels

To limit access to the user configuration interface, security codes are assigned to different menu levels. Make security codes available to operators, maintenance crew, supervisors, etc. according to what func- tion level you want for each group. Security Level C is not recom- mended for most users. Gain access to configuration menus using the following codes.

Security Level

Security Code

Function

 

 

 

A

All Values

Allows adjustment of

 

 

the Set Point

B

458

Basic menus

C

736

Calibration menus

Configuration Menus

The following configuration menus can be accessed through the user interface (see Configuration, page 12).

Menu

Adjustable

Factory

Security

Code Function

Range

Default

Level

 

 

 

 

Security Lock

0-999

458

A

Process Variable Display

Read Only

N/A

A

Displays the actual process

°

°

 

 

temperature.

F or

C

 

 

 

 

 

 

Process Set Point Adjust

Sensor Range

0°F

A

Adjusts the target process

°

°

 

 

 

F or

C

 

 

temperature.

Proportional Band

Temperature range above/below set point where proportional control is active. Most applications require a band between 10 to 200°F. This menu is active only when the dip switch is set to “PI”

1 to Sensor 25 B Span Maximum

°F or °C

Automatic Reset

0.0 to 100.0

0.1

B

Control feature that

Repeats/Min.

 

 

automatically corrects for small temperature offsets that occur in proportional control. The higher the setting, the faster the correction occurs. A high setting could cause overshoot during start-up. A low setting will not allow process temperature to reach to set point quickly enough. A setting of “0” turns off automatic reset. This menu is active only when the dip switch is set to “PI”.

CN 2110

14

Section 4–Adjusting Set Point and Configuration

Image 18
Contents User’s Guide Omega.com CN 2110 Temperature Controller Table of ContentsPage Quick Setup Setting the Sensor and Control ModeAdjusting the Set Point Introduction Inspection and UnpackingModel Identification Installation and Wiring Sensor and Control Type Selection SwitchesMounting Removing Mounting CollarsMount the CN Controller will now be held firmly in placeGood Wiring Practices Sensor Input Wiring Sensor Wiring Notes Thermocouple InputsSensor Input Wiring Three-Wire RTD InputsTwo-Wire RTD Inputs Control Output Wiring R20 20 Amp Relay Output WiringDC Solid State Relay Drive, 24Vdc, 40mA Output Wiring Instrument Power Wiring Adjusting Set Point and Configuration Adjusting the Set PointConfiguration Exit Configuration 5Move to .6until SP is next menu DisplayedConfiguration Menus Security Codes and LevelsOFF Control and Alarm Operation Control Operation Alarm Operation optionalTuning PI Control Module Option Descriptions Module InstallationReplacing Output Modules RemovalReplacement Auto Cycle TimeCalibration Offset Factory Default Recovery To reestablish the factory default valuesCalibration Calibration Factory Calibration Recovery Calibration NotesSensor Calibration Specifications Control AdjustmentsTroubleshooting Symptom Probable Cause Correction StepsTroubleshooting FAn FAIL, CNPage Page Page USAWARRANTY/DISCLAIMER Temperature