Omega

Section 3—Installation and Wiring

Sensor and Control

Type Selection

Switches

Set the CN 2110 controller’s configuration via mechanical dip switches, located on the bottom of the unit. Factory settings are J, TC, °F, and PI Control. Switches are easier to set before mounting.

To change the switch settings, first disconnect all wiring and power from the unit. Adjust switch settings as follows:

 

 

Setting

Factory

Switch

Function

Options

Setting

A

Thermocouple

J or K

J

B

Input Type

TC or RTD

TC

C

Temperature Units

°F or °C

°F

D

Control Type

ON-OFF or PI

PI

If input type is thermocouple, switch A selects either thermocouple type J or K.

Switch B selects input type thermocouple or RTD (resistance tempera- ture detector). Note: If RTD is selected, switch A is ignored.

Switch C selects temperature units °F or °C.

Switch D selects either PI (Proportional-Integral) or ON-OFFcontrol.

J

RTD

˚C

ONOF

K

TC

˚F

PI

J

RTD

˚C

ONOF

K

TC

˚F

PI

Figure 3.1

Default Dip Switch Settings

CN 2110

4

Section 3–Installation and Wiring

Image 8
Contents User’s Guide Omega.com CN 2110 Temperature Controller Table of ContentsPage Adjusting the Set Point Quick SetupSetting the Sensor and Control Mode Introduction Inspection and UnpackingModel Identification Installation and Wiring Sensor and Control Type Selection SwitchesMounting Removing Mounting CollarsMount the CN Controller will now be held firmly in placeGood Wiring Practices Sensor Input Wiring Sensor Wiring Notes Thermocouple InputsTwo-Wire RTD Inputs Sensor Input WiringThree-Wire RTD Inputs DC Solid State Relay Drive, 24Vdc, 40mA Output Wiring Control Output WiringR20 20 Amp Relay Output Wiring Instrument Power Wiring Configuration Adjusting Set Point and ConfigurationAdjusting the Set Point Exit Configuration 5Move to .6until SP is next menu DisplayedConfiguration Menus Security Codes and LevelsOFF Tuning PI Control Control and Alarm OperationControl Operation Alarm Operation optional Module Installation Replacing Output ModulesModule Option Descriptions RemovalReplacement Auto Cycle TimeCalibration Calibration Offset Factory Default RecoveryTo reestablish the factory default values Sensor Calibration Calibration Factory Calibration RecoveryCalibration Notes Specifications Control AdjustmentsTroubleshooting Symptom Probable Cause Correction StepsTroubleshooting FAn FAIL, CNPage Page Page USAWARRANTY/DISCLAIMER Temperature