Section 3—Installation and Wiring
Sensor and Control
Type Selection
Switches
Set the CN 2110 controller’s configuration via mechanical dip switches, located on the bottom of the unit. Factory settings are J, TC, °F, and PI Control. Switches are easier to set before mounting.
To change the switch settings, first disconnect all wiring and power from the unit. Adjust switch settings as follows:
|
| Setting | Factory |
Switch | Function | Options | Setting |
A | Thermocouple | J or K | J |
B | Input Type | TC or RTD | TC |
C | Temperature Units | °F or °C | °F |
D | Control Type | PI |
If input type is thermocouple, switch A selects either thermocouple type J or K.
Switch B selects input type thermocouple or RTD (resistance tempera- ture detector). Note: If RTD is selected, switch A is ignored.
Switch C selects temperature units °F or °C.
Switch D selects either PI