Chromalox CN2110 manual Troubleshooting, FAn FAIL, CN

Page 27

CN 2110 Temperature Controller

Troubleshooting

continued

 

Symptom

Probable Cause

Correction Steps

 

 

 

 

 

 

 

Process not

1.

Incorrect settings

1.

Check Proportional

 

in control

2.

Thermocouple

 

Band setting and

 

 

 

Automatic Reset

 

 

 

Wiring

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

2.

Check thermocouple

 

 

 

 

 

polarity

 

 

 

 

 

 

 

Instrument continu-

1.

Severe electrical

1.

Separate sensor wiring

 

ally goes through

 

noise

 

from other wiring

 

power-up reset

 

 

2.

Apply power line filter

 

 

 

 

3.

Contact Omega

 

 

 

 

 

 

Display reads

1. Fan for T10 output

1.

Check for and clear any

 

FAn FAIL, CN

 

has failed

 

obstruction in fan, then

 

2110 disables

 

 

 

power unit up and

 

control output

 

 

 

check display

 

 

 

 

2.

Discontinue operation,

 

 

 

 

 

replace fan assembly,

 

 

 

 

 

or return to Omega for

 

 

 

 

 

replacement

Section 9–Troubleshooting

23

CN 2110

Image 27
Contents User’s Guide Omega.com Table of Contents CN 2110 Temperature ControllerPage Quick Setup Setting the Sensor and Control ModeAdjusting the Set Point Inspection and Unpacking IntroductionModel Identification Sensor and Control Type Selection Switches Installation and WiringRemoving Mounting Collars MountingController will now be held firmly in place Mount the CNGood Wiring Practices Thermocouple Inputs Sensor Input Wiring Sensor Wiring NotesSensor Input Wiring Three-Wire RTD InputsTwo-Wire RTD Inputs Control Output Wiring R20 20 Amp Relay Output WiringDC Solid State Relay Drive, 24Vdc, 40mA Output Wiring Instrument Power Wiring Adjusting Set Point and Configuration Adjusting the Set PointConfiguration 5Move to .6until SP is next menu Displayed Exit ConfigurationSecurity Codes and Levels Configuration MenusOFF Control and Alarm Operation Control Operation Alarm Operation optionalTuning PI Control Removal Module InstallationReplacing Output Modules Module Option DescriptionsAuto Cycle Time ReplacementCalibration Offset Factory Default Recovery To reestablish the factory default valuesCalibration Calibration Factory Calibration Recovery Calibration NotesSensor Calibration Control Adjustments SpecificationsSymptom Probable Cause Correction Steps TroubleshootingFAn FAIL, CN TroubleshootingPage Page Page USAWARRANTY/DISCLAIMER Temperature