Chromalox CN2110 manual Specifications, Control Adjustments

Page 25

CN 2110 Temperature Controller

Section 8—Specifications

Control Modes

ON/OFF; PI—Proportional with integral

Control Adjustments

 

Proportional Band

1 to sensor span maximum

Automatic Reset

0.0 to 100.0 repeats/minute

Cycle Time

0.1 to 60.0 seconds

On/Off Deadband

1° to 100°F or °C

Set Point Upper Limit

sensor range °F or °C

Set Point Lower Limit

sensor range °F or °C

Output Limit

0 to 100%

Alarm Adjustments

 

Type

Absolute High or Low

Set Point

Sensor range °F or °C

Alarm Dead Band

0° to 100°F or °C

Control/Alarm Outputs

 

Relay (R1)

1 Amp Form A, 120/240VAC

Relay (R20)

Form A, 120/240VAC resistive loads at 30 sec. cycle time

 

20 Amps, 500,000 Operations

 

15 Amps, 1 Million Operations

 

10 Amps, 5 Million Operations

 

5 Amps, 5 Million Operations

Solid State Relay Drive (DC)

24VDC at 40mA

Solid State Relay (T1)

1A Triac, up to 240VAC

Solid State Relay (T5)

5A, up to 240VAC at 40°C

Solid State Relay (T10)

10A, up to 240VAC at 40°C

Alarm

Form C, Relay 5 Amps at 120VAC,

 

2.5A at 240VAC

Sensor Input

Switch selectable; J,K Thermocouple; RTD

Input Update Rate

Four samples per second

Input Specifications

Range °F

J TC

-100 to 1400°F

K TC

-100 to 2400°F

100Pt RTD (a=.00385)

-200 to 1000°F

Readout Stability

 

Range °C -73 to 760°C -73 to 1316°C -128 to 538°C

Accuracy at 77°F ambient 0.2% Span +/-1 least significant digit 0.2% Span +/-1 least significant digit 0.2% Span +/-1 least significant digit

J and K TC

+/-1°F per 10°F change in ambient temperature

RTD

+/-0.5°F per 10°F change in ambient temperature

Open Sensor and

 

Out-of-Range Conditions

Displays “SEnS”, Control output 0%

Instrument Power

90 to 260VAC Less than 10 VA

Operating Environment

0° to 65°C (32° to 150°F)

Dimensions

 

Overall

4.0 x 4.0 x 4.0 inches (102 mm)

Depth Behind Display

3.6 inches (92 mm)

Front Panel Projection

0.4 inches (10 mm)

Panel Cutout

3.6 x 3.6 inches (92 mm x 92 mm)

Enclosure Material

High temp ABS plastic rated for 0° to 175°F

Front Panel

NEMA 4X construction, requires surface finish not rougher

 

than 0.000032 inch

Influence of Line Voltage Variation ....

+/-0.1% of sensor span per 10% change in

 

nominal line voltage

Noise Rejection

Less than 2°F with 240 VAC, 60 Hz applied from sensor

Common Mode Noise

 

input to earth ground

Series Mode Noise

Less than 2°F with 100mV, peak to peak series mode noise

RFI

Typically less than 0.5% of sensor span at distance

 

of 1 meter (3.1 feet) from a transmitter of 4W at 464MHz

Sensor Leadwire Effect

+1°F for 1000 feet of 18 AWG thermocouple extension wire

J Thermocouple

K Thermocouple

+2°F for 1000 feet of 18 AWG thermocouple extension wire

RTD

+/-0.1% of sensor span per 20balanced leadwire resistance

 

(20is the total loop resistance)

Section 8–Specifications

21

CN 2110

Image 25
Contents User’s Guide Omega.com Table of Contents CN 2110 Temperature ControllerPage Setting the Sensor and Control Mode Quick SetupAdjusting the Set Point Inspection and Unpacking IntroductionModel Identification Sensor and Control Type Selection Switches Installation and WiringRemoving Mounting Collars MountingController will now be held firmly in place Mount the CNGood Wiring Practices Thermocouple Inputs Sensor Input Wiring Sensor Wiring NotesThree-Wire RTD Inputs Sensor Input WiringTwo-Wire RTD Inputs R20 20 Amp Relay Output Wiring Control Output WiringDC Solid State Relay Drive, 24Vdc, 40mA Output Wiring Instrument Power Wiring Adjusting the Set Point Adjusting Set Point and ConfigurationConfiguration 5Move to .6until SP is next menu Displayed Exit ConfigurationSecurity Codes and Levels Configuration MenusOFF Control Operation Alarm Operation optional Control and Alarm OperationTuning PI Control Replacing Output Modules Module InstallationModule Option Descriptions RemovalAuto Cycle Time ReplacementTo reestablish the factory default values Calibration Offset Factory Default RecoveryCalibration Calibration Notes Calibration Factory Calibration RecoverySensor Calibration Control Adjustments SpecificationsSymptom Probable Cause Correction Steps TroubleshootingFAn FAIL, CN TroubleshootingPage Page Page USAWARRANTY/DISCLAIMER Temperature