White Rodgers 36h Installation, Main Piping connections, LP GAS Conversion, Pilot Gas Connection

Page 4

INSTALLATION

Main Piping connections

NOTE

Refer to warnings and cautions on page 3 before attempting installation. All piping must comply with local codes, ordinances, and/or national fuel gas codes.

1.Turnoffelectricalpowertothesystematthefuse box or circuit breaker. Also turn off the main gas supply.

2.If replacing an existing valve, disconnect all plumbing and electrical connections from the old control.

3.Thisvalvemaybeinstalledupright,+or–90˚from upright, or vertical (refer to fig. 1).The arrows on the valve identification label and on the bottom plate indicate direction of gas flow through the valve.

4.You should use new pipe that is properly cham- fered, reamed, and free of burrs and chips. If you are using old pipe, be sure it is clean and free of rust, scale, burrs, chips, and old pipe joint compound.

5.Apply pipe joint compound (pipe dope) or teflon tape that is approved for all gases, only to the male threads of the pipe joints. DO NOT apply compound or teflon tape to the first two threads (see fig. 3 for typical piping connections).

6.Do not tighten piping excessively, as this may damage the valve (50 ft lbs max).

7.See SYSTEM WIRING when making electrical connections. After all gas and electrical connec- tions are completed, turn gas on and check for gas leaks with leak detection solution or soap suds. Bubbles forming indicate a leak. SHUT

OFF GAS AND FIX ALL LEAKS IMMEDIATELY.

LP GAS CONVERSION

For LP gas conversion, use the LP conversion kit supplied with this control. Refer to the instruc- tions packed with LP conversion kit.

Pilot Gas Connection

These gas valves are shipped with the pilot outlet plugged. For installations requiring pilot gas (Proven/Intermittent Pilot Systems), remove the plug from the pilot gas outlet (see fig. 2) and use the fitting packed separately with the valve.

Install the fitting into the pilot gas outlet, turning until finger tight. Insert clean, de-burred 1/4" O.D. tubing all the way through the fitting. While hold- ing the tubing securely, slowly tighten the fitting until you feel a slight “give”. Tighten the fitting an additional 1-1/2turns.

The plug should not be removed for a Direct Burner Ignition system such as Direct Spark or Hot Surface Ignition.

Refer to page 7 for pilot flame adjustment infor- mation.

NOTE

All piping must comply with local codes, ordinances, and/or national fuel gas codes.

NOTE: A MANUAL SHUTOFF VALVE MUST BE INSTALLED WITHIN 6 FEET OF THE EQUIPMENT

Drop

Horizontal

3 in.￿

 

 

 

Gas Valve

minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Piped Gas

Supply

NOTE: ALWAYS INCLUDE A

DRIP LEG IN PIPING

 

Drop

 

Gas Valve

Horizontal

 

Riser

 

 

3 in.￿

3 in.￿

Gas Valve

minimum

Riser minimum

 

Piped Gas

Tubing Gas

 

Supply

Supply

 

4

Figure 3. Typical Gas Valve Piping

Image 4
Contents Specifications Installation InstructionsContents DescriptionParts and Accessories Mounting PositionsUpright, or 0 to 90 from upright Left or Right Inlet BossPrecautions Donotbegininstallationuntilyoureadthefollowing PrecautionsInstallation Main Piping connectionsLP GAS Conversion Pilot Gas ConnectionSystem Wiring SeeTypical Wiring for Proven/Intermittent Pilot System Adjustment Pressure Regulator AdjustmentPilot Flame Adjustment Outlet Pressure AdjustmentForyour Safety Read Before Operating Lighting InstructionsOperating Instructions To Turn OFF GAS to ApplianceDescription Instructions D’INSTALLATIONSpécifications Pièces et accessoires Positions DE MontageVerticale, ou de 0 à 90 de la verticale Gauche ou Droite Entrée BossPrécautions AvertissementPrincipaux raccords de tuyaux Conversion AU GPLBranchement DU GAZ Pour UNE Flamme Pilote Immédiatement Toutes LES FuitesCâblage DU Système Caractéristiques et identification des bornesCâblage typique pour système d’allumage par surface chaude Ajustement Ajustement DU Régulateur DE PressionRéglage de la pression De sortie Ajustement de la Flamme piloteInstructions D’ALLUMAGE Pour Votre SÉCURITÉ, Lire Avant L’UTILISATIONInstructions D’UTILISATION Pour Couper L’ALIMENTATION DE GAZ DE L’APPAREILInstrucciones DE Instalación DescripciónEspecificaciones ContenidoEspecificaciones Piezas y accesoriosPosiciones DE Montaje Recta, o 0 a 90 de la posición recta Izquierda o DerechaPrecauciones Pérdida de vidasInstalación Conexiones de las tuberías principalesConversión Para GAS DE Petróleo Licuado Conexión para gas con pilotoPrincipal MP del puente externo ver las figs y Conexiones DEL SistemaConecte los cables consecuentemente ver las figs y Instalación ControladorAjuste Ajuste DEL Regulador DE PresiónAjuste de presión de salida Ajuste de la llama del pilotoInstrucciones DE Encendido POR SU Seguridad LEA Antes DE UsarInstrucciones DE USO Para Cerrar EL GAS QUE Llega AL Artefacto