Outback Power Systems GFX1448E, GFX1424E, GFX1312E manual Volt Inverter Settings Mate, Input

Page 50

Specifications

 

Table 18

24-Volt Inverter Settings (MATE)

 

 

Field

Item

 

Default

Minimum

 

Maximum

 

search sensitivity (see page 14 for increments)

6

0

 

50

Search

search pulse length

 

8

4

 

20

 

search pulse spacing

 

60 AC cycles

4 AC cycles

 

120 AC cycles

 

ac transfer control

 

Grid

 

Grid or Gen

Input

ac1/grid limit

 

25 Aac

2.5 Aac

 

30 Aac

 

ac2/gen limit

 

25 Aac

2.5 Aac

 

30 Aac

 

low battery cut-out (LBCO)

 

21 Vdc

18 Vdc

 

24 Vdc

Inverter

low battery cut-in (LBCI)

 

25 Vdc

20 Vdc

 

28 Vdc

 

adjust output voltage

 

230 Vac

210 Vac

 

250 Vac

 

charger limit

 

5.5 Aac

0 Aac

 

6 Aac

Charger

absorb voltage

 

28.8 Vdc

26 Vdc

 

32 Vdc

absorb time limit

 

1.0 hours

0.0 hours

 

24.0 hours

 

 

 

 

float voltage

 

27.2 Vdc

24 Vdc

 

30 Vdc

 

float time period

 

1.0 hours

0.0 hours

 

24.0 hours

 

refloat voltage

 

25 Vdc

24 Vdc

 

26 Vdc

 

equalization voltage

 

29.2 Vdc

28 Vdc

 

34 Vdc

 

equalization time period

 

1.0 hours

0.0 hours

 

24.0 hours

 

 

 

 

 

 

 

 

ac1/grid lower limit

 

208 Vac

140 Vac

 

220 Vac

Grid

ac1/grid upper limit

 

252 Vac

250 Vac

 

280 Vac

ac1/grid input limit

 

25 Aac

2.5 Aac

 

30 Aac

 

 

 

 

ac1/grid transfer delay

 

6 AC cycles

0 AC cycles

 

240 AC cycles

 

gen input connect delay

 

0.5 minutes

0.2 minutes

 

15 minutes

 

ac2/gen lower limit

 

208 Vac

140 Vac

 

220 Vac

Generator

ac2/genupper limit

 

252 Vac

250 Vac

 

280 Vac

(Gen)

ac2/gen input limit

 

25 Aac

2.5 Aac

 

30 Aac

 

ac2/gen transfer delay

 

6 AC cycles

0 AC cycles

 

240 AC cycles

 

ac2/gen support

 

ON

 

ON or OFF

 

aux output control

 

AUTO

ON, OFF, or AUTO

 

aux output function

 

Cool Fan

Cool Fan, DivertDC, DivertAC, AC Drop, Vent

 

 

Fan, Fault, GenAlert, LoadShed, or Remote

 

 

 

 

 

genalert on voltage

 

22 Vdc

20 Vdc

 

28 Vdc

 

genalert on delay

 

4 minutes

0 minutes

 

240 minutes

Auxiliary

genalert off set point

 

28 Vdc

24 Vdc

 

36 Vdc

(AUX)

genalert off delay

 

9 minutes

0 minutes

 

240 minutes

 

load shed off voltage

 

22 Vdc

20 Vdc

 

28 Vdc

 

vent fan on set point

 

26 Vdc

20 Vdc

 

32 Vdc

 

vent fan off period

 

5 minutes

0 minutes

 

30 minutes

 

diversion on voltage

 

29.2 Vdc

24 Vdc

 

32 Vdc

 

diversion off delay

 

30 seconds

0 seconds

 

240 seconds

Stacking

stack phase

 

Master

Master, OB Slave L1, 3p Classic B, 3p Classic C

Power

master adjust only

 

0

0

 

7

Save

slave adjust only

 

1

1

 

15

 

sell re volts

 

26 Vdc

20 Vdc

 

30 Vdc

Sell

grid tie window

 

User

 

IEEE or User

 

grid tie authority

 

GridTie

GridTie or NoSell

Calibration

vac input adjustment3

 

236

220

 

254

vac output adjustment3

 

236

220

 

254

(Cal)

 

 

battery vdc adjustment4

 

2

0

 

4

 

 

 

3These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower voltages. One count equals approximately 1 Vac. The range of adjustment is 15 Vac above nominal and 17 Vac below nominal.

4These values are in digital counts, not volts. One count equals 0.2 Vdc. The range of adjustment is 0.4 Vdc above or below nominal.

48

900-0112-01-00 Rev B

Image 50 Contents
International Series GFX Inverter/Charger GFX1312E GFX1424E GFX1448ETrademarks Audience Symbols UsedGeneral Safety Term Definition DefinitionsTerms and Definitions Table of Contents Table of Contents List of Tables List of FiguresPage Welcome to OutBack Power Technologies IntroductionSystem Display and Controller MATE3 and Mate System Display and ControllerFunctional Test Pre-startup ProceduresCommissioning StartupPowering Down Adding New DevicesOperation LED IndicatorsBattery LED Values Operation Status LED Quick ReferenceDescription of Functions InvertingSearch InputAC Current Settings AC Source AcceptanceGenerators TransferInput Support Bulk Stage Battery ChargingNo Charging Absorption Stage SellFloat Stage Float TimerSilent Repeated SilentNew Absorption Stage Absorption TimerNew Charging Cycle Repeated Charging CyclesBattery Temperature Compensation EqualizationExamples Selling Multiple-Inverter Installations Stacking OutBack HUB4 and MateThree-Phase Stacking Parallel Stacking Dual-Stack and LargerPower Save Levels Auxiliary Terminals Operation Advanced Generator Start AGS High Battery Transfer HBXSystem Display-Based Functions Grid Use ProgrammingTroubleshooting Basic TroubleshootingTroubleshooting User To Gen in the AC Input and Current Limit Limits or Gen AC Input Voltage Limits Terminals with a DC voltmeter. If voltage is Error Messages Error TroubleshootingMessage Definition Possible Remedy Acin freq too highDisconnect Messages Acin voltage maxSelling or Charging Stopped Stop Sell and Charge Reasons Code DefinitionProgrammed setting. It cannot charge or sell Stop Sell and Charge ReasonsPage Electrical Specifications GFX1312E Value SpecificationsSpecifications for Model GFX1312E Mechanical Specifications GFX1312EMechanical Specifications GFX1424E Specifications for Model GFX1424EElectrical Specifications GFX1424E Value Mechanical Specifications GFX1448E Specifications for Model GFX1448EElectrical Specifications GFX1448E Value Environmental Specifications for All Models Value Environmental SpecificationsRegulatory Specifications Grid-Interactive UseDefault Settings and Ranges viewed in Mate 12-Volt Inverter Settings MateVolt Inverter Settings Mate Input48-Volt Inverter Settings Mate Battery vdc adjustment26Default Settings and Ranges viewed in MATE3 Volt Inverter Settings MATE324-Volt Inverter Settings MATE3 Vent Fan Enable VoltageStacking Power Save OutBack Power Technologies Product RegistrationProduct Registration Warranty Year Limited Warranty for GFX ProductsReturn Material Authorization RMA How to Arrange for Warranty ServiceTroubleshooting Contacting OutBackOut of Warranty Returning Product to OutBackThis page intentionally left blank Index AUX FunctionsIndex Index Arlington, WA 98223 USA +1.360.435.6030