Nordyne RC 92+, RL 90+ Vent Termination Clearances for Direct Vent Furnaces

Page 23

 

VENT TERMINAL

AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

 

 

 

 

 

 

 

 

 

Canadian Installations1

 

US Installations2

A =

Clearance above grade, veranda, porch,

12 inches (30 cm)

 

12 inches (30 cm)

 

deck, or balcony

 

 

 

 

 

 

 

 

B =

Clearance to window or door that may be

6 inches (15 cm) for appliances 10,000

6 inches (15 cm) for appliances 10,000

 

opened

 

Btuh (3 kW), 12 inches (30 cm) for

Btuh (3 kW), 9 inches (23 cm) for

 

 

 

appliances > 10,000 Btuh (3 kW) and

appliances > 10,000 Btuh (3 kW) and

 

 

 

100,00 Btuh (30 kW), 36 inches (91 cm)

50,000 Btuh (15 kW), 12 inches (30 cm)

 

 

 

for appliances >100,00 Btuh (30 kW)

for appliances > 50,000 Btuh (15 kW)

 

 

 

 

 

C =

Clearance to permanently closed window

*

 

*

D =

Vertical clearance to ventilated soffit

 

 

 

 

 

located above the terminal within a

 

*

 

*

 

horizontal distance of 2 feet (61 cm) from

 

 

 

 

 

 

the center line of the terminal

 

 

 

 

E =

Clearance to unventilated soffit

 

*

 

*

F =

Clearance to outside corner

 

*

 

*

G =

Clearance to inside corner

 

*

 

*

H =

Clearance to each side of center line

 

3 feet (91 cm) within a height 15 feet

*

 

extended above meter/regulator assembly

above the meter/regulator assembly

 

 

I =

Clearance to service regulator vent outlet

3 feet (1.83 m)

 

*

J =

Clearance to nonmechanical air supply inlet

6 inches (15 cm) for appliances 10,000

6 inches (15 cm) for appliances 10,000

 

to building or the combustion air inlet to any

Btuh (3 kW), 12 inches (30 cm) for

Btuh (3 kW), 9 inches (23 cm) for

 

other appliance

 

appliances > 10,000 Btuh (3 kW) and

appliances > 10,000 Btuh (3 kW) and

 

 

 

100,00 Btuh (30 kW), 36 inches (91 cm)

50,000 Btuh (15 kW), 12 inches (30 cm)

 

 

 

for appliances >100,00 Btuh (30 kW)

for appliances > 50,000 Btuh (15 kW)

 

 

 

 

 

K =

Clearance to a mechanical air supply inlet

6 feet (1.83 m)

 

3 feet (91 cm) above if within 10 feet

 

 

 

 

 

(3 m) horizontally

 

 

 

 

 

L =

Clearance above paved sidewalk or paved

7 feet (2.13 m) †

 

*

 

driveway located on public property

 

 

 

 

 

 

 

 

 

 

 

 

 

M =

Clearance under veranda, porch deck, or

12 inches (30 cm) ‡

 

*

 

balcony

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code

2In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

*For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA B149.1, the following statement shall be included:

“Clearance in accordance with local installation codes, and the requirements of the gas supplier and the manufacturer’s installation instructions.”

Figure 19. Vent Termination Clearances for Direct Vent Furnaces

23

Image 23
Contents What to do if YOU Smell GAS Installation InstructionsPage Table of Contents Furnace Specifications Downflow *RL Furnace G6RC Upflow Furnace Capacities -Furnace Airflow DataCapacities Important Note Safety InformationInstallation Requirements Requirements and Codes Minimum Clearances to Combustible Material Clearances to Combustible MaterialsLocation Horizontal InstallationsDownflow Warning *RL Models Vinyl Cap Grey Tubing Circulating AIR Supply Supplyair Plenum InstallationInstallation on a concrete slab *RL Installation on a combustible floor *RLVenting and Combustion AIR Requirements Return AirFurnace on a Wood Floor Downflow Sub-Base DimensionsEquipment in a Confined Combustion Air Quality Air Requirements For One-Pipe InstallationInstallation In An Unconfined Space Installation In a Confined SpaceVenting Requirements Seal any unused openings in the vent- ing system SolutionVent Pipe Material Vent Pipe Length and DiameterVent Table Upflow FurnacesDownflow Furnaces Horizontal Venting Vent Pipe InstallationPipe Routing and Support Location of Outdoor TerminationsVertical Venting Page Vent Termination Clearances for Direct Vent Furnaces For appliances 100,00 Btuh 30 kW Vent Protection Vertical VentingUpflow Models = 12 Above Roof or Snow Accumulation LevelVent Freezing Protection Side Wall Vent Kit Drainage of Condensate from FurnaceConcentric Vent Termination Leak Check GAS Supply and PipingAbove Sea Level Manifold Pressure in WC for Natural Gas at Various AltitudesLP/Propane Gas Sea Level and High Altitude Conversion ConversionHigh Altitude Application Natural Gas High Altitude ConversionLow Voltage Wiring Electrical WiringLine Voltage Wiring Firing rate = 1040 x 90 = 93,600 Btuh START-UP and AdjustmentsStart-Up Procedure Verifying and Adjusting Firing RateBlower Speed Tap Location Verifying and Adjusting Temperature RiseGas Flow Rate Verifying Operation of the Supply Air Limit SwitchVerifying Burner Operation Description of ComponentsMaintenance WD# For Upflow and Downflow Residential FurnacesDownflow Furnace Models Upflow Furnace ModelsSequence of Operation Heating ModeSystem Operation Information Twinning of Two Furnaces Cooling ModeFan Mode Furnace Fails to OperateFuel Type INSTALLATION/PERFORMANCE Check List