NOTE: Industry research studies indicate that when condensate is routed to an active drain, household detergents, etc., buffer its acidity. If the drain is not actively used or if codes require, obtain a neutralizer kit (usually contains lime- stone). Proper drains and connections to the condensate tubing are required as NORDYNE cannot be held responsible for water leakage which occurs due to loose hose connections or improperly sealed drain line pipes.
GAS SUPPLY AND PIPING
This furnace is equipped for either left or right side gas entry. Typical gas service
All gas piping must be installed in compliance with local codes and utility regulations. Some local regulations require the installation of a manual main
An 1/8” NPT plugged tap must be installed in the gas line to the unit for use when measuring the gas supply pressure. The plug should be readily accessible for service use. A drip leg should be installed in the vertical pipe run to the unit.Table 5 lists gas flow capacities for standard pipe sizes as a function of length in typical applications based on nominal pressure drop in the line.
NOTE: Gas piping must not be run in or through air ducts, chimneys, gas vents, elevator shafts, etc.
Compounds used on threaded joints of gas pip- ing must be resistant to the actions of liquefied petroleum gases.
The main manual gas valve and main power dis- connect to the furnace must be properly labeled by the installer in case emergency shutdown is required.
!CAUTION:
Do not use matches, lighters, candles, or other sources of open flame to check for gas leaks.
Leak Check
!WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connec- tions. A fire or explosion may result causing property damage, personal injury or loss of life.
After the gas piping to the furnace is complete, all connections must be tested for gas leaks. To check for leaks use only a soap and water solution or other approved method.
IMPORTANT NOTE: When pressure testing gas supply lines at pressures greater than 1/2 psig (14 in. water column), the furnace must be disconnected from the gas supply piping system to prevent damage to the gas control valve. If the test pressure is less than or equal to 1/2 psig (14 in. water column), the furnace must be isolated from the gas supply line by closing the manual
!WARNING:
This furnace was equipped at the factory for use with natural gas only. A special kit, supplied by the manu- facturer, is required to convert the furnace to operate on LP/propane gas. Failure to use the proper conversion kit can cause fire, explosion, property damage, carbon monoxide poisoning, personal injury, or death.