1.1Operating Modes

 

The SIMATIC 505±2557 Sixteen Channel RTD Input Module is a member of

 

Siemens's family of I/O modules compatible with the SIMATIC 505 series

 

programmable controllers. The SIMATIC 505±2557 is designed to translate

 

10 Ohm copper, 100 Ohm platinum and, 120 Ohm nickel RTDs or millivolt

 

input signals into scaled digital words which are then sent to the

 

programmable controller (PLC).

 

The SIMATIC 505±2557 RTD Input Module features built±in independent

 

two, three, or four lead compensation for each RTD input. Support for other

 

RTD types is available through special request from the factory. For

 

technical assistance, contact your Siemens Energy & Automation, Inc.,

 

distributor or sales office.

Asynchronous

The module operates asynchronously with respect to the PLC; a scan of the

Operation

PLC and input sampling of the module do not occur at the same time.

 

Instead, the module will translate all inputs in one module update (20

 

milliseconds maximum) and store the translated words in a buffer memory.

 

The PLC retrieves the stored words from the module buffer memory at the

 

start of the I/O scan.

Compatability with

The SIMATIC 505±2557 has been tested and is compatible with the

Immediate I/O

Immediate read function of the SIMATIC 545 and 555 PLC.

100 Ohm, 10 Ohm,

Each of the module's 16 channels may be configured to receive either a 100

120 Ohm RTDs, or

Ohm platinum RTD or a 120 Ohm nickel RTD or a 10 Ohm copper RTD

Millivolt Inputs

input signal (two, three or four wire) or a DC voltage signal ranging from 0

 

to 100 millivolts. Selection of 10 Ohm, 100 Ohm or 120 Ohm RTDs or

 

millivolts are made via internal switch and jumper settings.

1-2

Description

SIMATIC 505±2557 Installation and Operation Guide

Image 12
Contents Simatic Copyright 1998 by Siemens Energy & Automation, Inc Manual Publication History List of Effective Pages Contents Iv Contents List of Figures List of Tables Preface Agency Approvals EuropeanCommunity CE ApprovalDescription 100 Ohm, 10 Ohm, 120 Ohm RTDs, or Millivolt InputsOperating Modes Word Input to the PLC from the Module RTD Input to Digital Conversion Scale UnitsSignals EffectOut-of-Range Input Effect of Voltage Input 10 Ohm Copper Resolution Input ResolutionInstalling and Configuring the Module Calculating the I/O Base Power BudgetSelecting 2 and 3 Wire or 4 Wire Operation Installing and Configuring the Module Configuring Temperature or SelectingMillivolt Input Selecting Degrees Celsius orFahrenheit Selecting DataConfiguration Jumper Locations Inserting Module IntoBase Wiring the Input Connectors Copper Wire Table at 25 Degrees CelsiusPress In Wiring Connector Wiring Diagram for 2, 3, or 4 Wire RTD Wiring Diagram for Millivolt Measurements Cable Grounding Example I/O Configuration Chart Advanced Function Programming Advanced Software Functions IntroductionOverview AdvancedSetting the Module ConfigurationJumper Logging Controller I/OMemory Internal Register Structures Input and Output Register OffsetsInput Registers Input Channel DataInput Flag Bits Peak/Valley Hold Input WordsOutput Data Registers AveragingFunction Enable Bits Control RegistersInputs Discrete Handshake Inputs Outputs Data Identification BitsLoading Data into the Simatic 505±2557 Module Data Loading ProcessSample Low and High Alarm Setpoints Identifying the Data Being Transferred 11 Enabling the Functions Loaded Loading Programs into the I/O Module 13 Startup Relay Ladder Logic Page When Using Timing Overhead for Functions EnabledTiming Considerations Timing ConstraintsDefault Values Default Function ValuesDefault Function Values for Simatic 505±2557 Additional Information about Each FunctionAlarm Setpoints DegreesCentigrade or Degrees FahrenheitDigital Filtering Averaging Peak and ValleyHold Hold Reset Flag BitsFunction PrecedenceTroubleshooting 10 Troubleshooting Flow Diagram Symptom Probable Cause Corrective ActionI/O Register Quick Reference 17 I/O Register Quick ReferenceOr K Memory Configuration Tables Page Addressing Worksheet Items Unique to the Simatic 505±2557 Module 18 Open RTD Status BitsTroubleshooting Specifications Table B-1 SpecificationsSpecifications subject to change without notice Jumper Settings Log Sheet Customer Response Business Reply Mail