Installing and Configuring the Module (continued)
Selecting | No hardware changes are required for millivolt inputs. To select millivolt | ||
Temperature or | input mode for an input turn OFF the M and L switch for the input channel. | ||
Millivolt Input | (See Figure | ||
| configure the M and L switch. |
| |
| M | L |
|
| 0 | 0 | Millivolt |
| 0 | 1 | 10 Cu |
| 1 | 0 | 100 Pt |
| 1 | 1 | 120 Ni |
NOTE: Each channel contains a jumper to select between 2, 3 and 4 wire RTD elements. (See Figure
Selecting 2 and 3 As shipped the module is ready to accept 2 and 3 wire RTDs. To configure
Wire or 4 Wire an input channel for 4 wire operation requires the following steps: Operation
1.Remove the 3 wire select jumper JP68±JP83 for the appropriate input channel and store on a single pin.
2.Move 2 input jumpers/channel to the 4 wire position. For example: To configure Channel 1, move JP1 and JP2 to the 4 wire position.
Selecting 10 Ohm If a 10 Ohm RTD is selected the gain of the input amplifier must be
RTD Inputsincreased to process the smaller signal levels. (See Figure
Selecting PLC Login Locate JP67 on the printed circuit board to select PLC Login Mode
Mode(See Figure
Selecting Digital Locate the Digital Filtering Jumper JP65 (See Figure
Filteringfiltering, set the jumper in the ENABLED position. Since many analog input signals contain noise, Siemens recommends using digital filtering unless maximum response time is required.