Desa VDCFTNA Ventilation AIR, Ventilation Air From Inside Building, Ventilation Air From Outdoors

Page 8

AIR FOR COMBUSTION

AND VENTILATION

Continued

Example:

 

30,000

 

Gas water heater

 

Btu/Hr

Vent-free fireplace

+

10,000

Btu/Hr

Total

=

40,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space can support)

__________ Btu/Hr (actual amount of Btu/Hr used) Example: 35,840 Btu/Hr (maximum the space

can support)

40,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the fireplace may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 4). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

 

 

12"

Ventilation

 

Ventilation Grills

Grills

 

Into Adjoining

Or

Into Adjoining Room,

Room,

Option 2

Remove

Option 1

 

Door into

 

 

 

 

Adjoining

 

 

Room,

 

 

Option

 

 

3

 

 

 

12"

Figure 4 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 5 - Ventilation Air from Outdoors

www.desatech.com113133-01C

Image 8
Contents Vdcfrpa and Vdcfrna Shown with Optional Cabinet Mantel/Hearth Base AccessoryThermostat Models Vdcftna and Vdcftpa Remote-Ready Models Table of Contents Safety Information Safety Information Optional Remote Control Accessories Product FeaturesProduct Identification Local CodesTools Required Phillips screwdriver Hood AssemblyAir for Combustion Ventilation Determining FRESH-AIR Flow for Fireplace Location AIR for Combustion VentilationProviding Adequate Ventilation Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Check GAS TypeInstallation Installation ItemsFireplace Clearances Fireplace pilot and burner must be at least 18 above floorBuilt-In Fireplace Installation If you have not installed hood, follow instruc- tions onOptional Mantel Installation Route flexible gas line through access hole in hearth baseRemoving Upper Louver Installing Optional Blower Accessory GA3450TACheck all gas connections for leaks. See Open lower louver door by swinging door down see Figure Installing Blower AccessoryRemove 4 screws from upper louver see . Save these screws For Built-In Installation Extension CordConnecting to GAS Supply External Regulator With Vent Pointing DownChecking GAS Connections Connecting equipment shutoff valve to heater controlInstallation Items Needed Pressure Testing Fireplace Gas Connections Equipment Shutoff ValveInstalling Receiver Installing 9-Volt Battery in Hand-Held Remote Control UnitRemove battery cover on back of remote control unit Replace battery cover onto remote control unitOptional Wall Switch GWMS2 Remote-Ready Models Only Remove jumper wire from control valve see ,Installing LOG SET and Screen For Your Safety Read Before LightingOperating Fireplace Lighting InstructionsManual Lighting Procedure Operating FireplaceTo Turn OFF GAS To Appliance Thermostat Control OperationAUTO/OFF/ON Blower Switch Operating BlowerDepress control knob and light pilot with match Optional Hand-Held Remote OperationOn/Off Series Model HRC100 Thermostat Series Model HRC200Optional GWMS2 Wall Mounted Switch Safety FeaturesAuto Shutoff Feature Key Pad Lock FeatureCleaning Maintenance Inspecting BurnersPilot Flame Pattern Burner Flame PatternCleaning Maintenance Wiring DiagramLOG Set CabinetTroubleshooting Observed Problem Possible Cause RemedyTroubleshooting When heated, vapors from Mote-Ready Models Only Power is lowSlight smoke or odor during Initial operation Processes and log curingGas leak. See Warning Specifications VDCFTPA, VdcfrpaIllustrated Parts Breakdown Firebox Models VDCParts List Vdcftpa and Vdcftna Illustrated Parts BreakdownThermostat Models Parts List REMOTE-READY Models Vdcfrna and VdcfrpaKEY THERMOSTAT-CONTROLLED Blower KIT GA3450T AccessoriesEquipment Shutoff Valve GA5010 Accessories WALL-MOUNT ON/OFF SwitchReceiver and HAND-HELD Thermostat Remote Control KIT HRC200 Receiver and HAND-HELD Remote Control KIT HRC100Replacement Parts Service HintsTechnical Service Parts Under Warranty113133-01C Limited Warranty VENT-FREE Compact Classic Hearth Warranty InformationKeep this Warranty