| To calculate the length of the system you need, add the equivalent | ||||||||||
Front Vent | Rear Vent |
|
|
|
|
|
| feet (meters) for each vent piece used in the system. | |||||||||||
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Vent Piece | 10" (25.4 cm) Round |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 45° elbow | 2.5 ft |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (0.8 m) |
90° elbow | 5.0 ft |
| (1.5 m) |
Example Vent System
A | B | B | A |
A. Left venting |
| A. Right venting |
|
B. 10" round 90° elbow | B. 10" round 90° elbow |
|
Roof Venting
AA
A. 10" (25.4 cm) round vent
Calculating Vent System Length
It is recommended that you use round vent instead of rectangular vent, especially if elbows are required. If rectangular vent is required, it should be transitioned to 10" (25.4 cm) round vent as soon as possible.
Maximum Length of Vent System
Vent | Length |
|
|
10" (25.4 cm) round | 40 ft (12.2 m) |
|
|
A | B | C |
A. External blower motor
B. Straight vent
C. 90° elbows
The following example falls within the maximum vent length of 40 ft (12.2 m).
2 - 90° elbows | = 10.0 ft (3 m) |
10 ft (3 m) straight | = 10.0 ft (3 m) |
|
|
Length of 10" (25.4 cm) system | = 20 ft (6 m) |
|
|
NOTE: The
Install Vent System
WARNING
Excessive Weight Hazard
Use two or more people to move and install downdraft vent.
Failure to do so can result in back or other injury.
1.Place cardboard or another form of covering on top of a flat surface where you can easily assemble the downdraft vent system.
2.Remove parts packages and downdraft vent from carton and set on covered surface.
3.Remove all shipping materials, tape and film from downdraft vent.
17