Electrical Requirements
IMPORTANT: Observe all governing codes and ordinances. Save Installation Instructions for electrical inspector’s use.
It is the customer’s responsibility to contact a qualified electrical installer, and to ensure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH
■This fan is suitable for use with solid state speed controls.
■A 120 Volt, 60 Hz., AC only
■Check with a qualified electrician if you are not sure the downdraft vent is properly grounded.
■The downdraft vent must be connected with copper wire only.
■The downdraft vent should be connected directly to the circuit breaker (or fused disconnect) box through flexible armored or nonmetallic sheathed copper cable. Allow some slack in the cable so the downdraft vent can be moved if servicing is ever necessary.
■Wire sizes (copper wire only) and connections must conform with the rating of the appliance as specified on the model/ serial rating plate located on the front of the downdraft vent above the wiring box cover.
■Wire sizes must conform to the requirements of the National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards
■Two UL listed or CSA approved ½" (12.7 mm) conduit connectors (Three are required if the
■A wiring diagram is located on the downdraft vent base above the power control board cover.
Venting Requirements
IMPORTANT: Make sure there is proper clearance within the wall or floor before making exhaust vent cutouts.
■Use heavy (rigid) metal vent.
■Venting system must terminate to the outside.
■Do not terminate the vent system in an attic or other enclosed area.
■Do not use 4" (10.2 cm)
■Do not install 2 elbows together.
■Do not use plastic or metal foil vent.
■The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.
■Use no more than three 90° elbows
■Make sure there is a minimum of 24" (61 cm) of straight vent between the elbows if more than one elbow is used.
■Use clamps to seal all joints in the vent system.
■Use caulking tape to seal the exterior wall or floor opening around cap.
■Do not cut joist or stud. If vent cutout falls over a joist or stud, a supporting frame must be constructed.
Flexible metal vent is not recommended. If it is used, calculate each foot of flexible vent as 2 ft (0.6 m) of rigid metal vent.
Flexible elbows count twice as much as standard elbows.
Recommended vent system length:
For either
7