Trane MUA-SVP01A-EN, Direct-Fired Indoor and Outdoor Make-Up Air Units manual MRT-Expert Controls

Page 10

Unit Operating Modes

to be "off" and the Cooling Night Setback function turns the unit "on", the unit will be cycled "off" once the room air temperature has fallen 2° below the Cooling Night Setback setpoint. The default for this setpoint is 100°F and is fixed at 27° above the Cooling setpoint. Changing the Cooling setpoint changes the Cooling Night Setback setpoint.

Auxiliary Unit Enable. The Auxiliary Unit Enable function overrides all other Auto Mode functions and automatically cycles the unit into operation. This function is activated whenever a contact is closed between the appropriate terminals on the unit's terminal strip located in the unit's main control panel. See the Typical Wiring Schematic and Multiplexed Input sections of this manual for more information. This function can be used with a twist timer, toggle switch, door switch, exhaust fan interlock, or any other dry contact to override the time clock schedule.

MRT-Expert Controls:

The AdaptAire MRT-Expert, modulating room temperature control, provides full information regarding unit operation and allows the user to adjust all operational parameters using the included BACview panel.

UNIT OFF MODE

Off Mode is the default unit operational mode. To place the unit in Off Mode scroll through the Unit Modes menu tree, locate the AUTO/OFF/MANUAL branch, and select OFF. This will place the unit in the OFF mode. The OFF mode prevents the fan and burner from starting. This mode will override the Time Clock and Night Setback functions.

UNIT MANUAL MODE

Manual Mode allows the supply fan to turn on regardless of the Time Clock or Night Setback functions. Heating and cooling functions use the Night Setback Setpoints. To place the unit in Manual Mode scroll through the Unit Modes menu tree, locate the AUTO/OFF/MANUAL branch, and select MANUAL. This will place the unit in the MANUAL mode.

UNIT AUTO MODE

Auto Mode has four different functions that control the supply fan and unit operation. They are a time clock function, heating and cooling night setbacks, and a signal from an external source to an auxiliary digital input. To place the unit in Auto Mode scroll through the Unit Modes menu tree, locate the AUTO/OFF/ MAN branch, and select AUTO. This will place the unit in the AUTO mode. This activates the four Auto mode functions.

Scheduling Time Clock. The primary Auto Mode function is the Time Clock Schedule. The Time Clock function allows the user to schedule the operational times of the unit. There are four different schedules available: 24 hour continuous operation, daily, holiday, and override. The daily schedule can be programmed

10

Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN

Image 10
Contents Controls Programming Guide JanuaryOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents Unit Operating Modes MDT ControlsMRT Controls MRT-Pro ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes Heating/Ventilating/Cooling Operating Modes Heating ModeGeneral Burner Control Unit Operating Modes Ventilation Mode Cooling Mode M P E R a T U R E S EManual Mode Damper Control ModesMixed Air Temperature Mode Building Pressure Mode Minimum Ventilation Functions100% Outside Air FreezestatUser Configured PID Control Direct Acting85ºF Reverse Acting Direct actingReverse acting Unit Resets Multiplexed InputsClock Set Critical Fault Codes DiagnosticsFault Code Low Discharge Temperature Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open Fault CODEBurner Status SOLUTIONIf fan is running check prior alarm logFault Code Burner Hand Diagnostics Non-Critical Fault Codes Fault Code Flame FailureSolution If fan is running Fault Code Unit off/Fan onSolution If fan is not running SOLUTIONIf fan/motor is running Fault CODEUnit on/Fan offSolution If fan/motor is not running Fault Code Check Airflow Switches Fault Code Clogged Filter Switch SOLUTIONIf clogged filter switch is closingFault CODEEnergy Save Mode SOLUTIONIf setpoints are misadjustedSOLUTIONIf setpoints are not misadjusted Solution If OAT, RoomT or DAT are such that heat is requiredDiagnostics Solution If setpoints are misadjusted Fault CODEInsufficient OASOLUTIONIf heat is desired SOLUTIONIf less outside air is desired Diagnostics Menu Selection Tree for BACview Menu SelectionUnit Modes Hotkey Menu Selection SET Points HotkeyAlarm History 64 Most Recent Alarm HotkeyResets Hotkey Status Menu HotkeyUser Configurable Output Hotkey Schedules HotkeyClockset Hotkey Help HotkeyFuel Select Hotkey Thermostat Output Curve Ohms Thermistor Output CurveAirflow Station Layout Airflow station layoutZone 583 Controller Specifications Network CommunicationZone 583 Controller Specifications Rnet MRT-Pro or Room Air sensorTypical Wiring Schematic Non-recirculating with evap Dfoa and Dfia model diagramTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane