Trane MUA-SVP01A-EN manual Damper Control Modes, Manual Mode

Page 16

Unit Operating Modes

To change the desired cooling room temperature of an MRT-Pro control system, depress the Warmer button to increase the desired room temperature setpoint or depress the Cooler button to decrease the desired room temperature setpoint.

Each push of a button changes the temperature setpoint by 1°F. The setpoint can be changed a maximum of ±10°F from the default of 72°F.

To change the desired cooling room temperature of an MRT-Expert control system, scroll through the SETPOINTS menu tree using the BACview, locate the Occupied Cooling Setpoint, and enter a new temperature. The allowable temperature range is 61°F - 96°F. The burner will modulate using a PID loop to maintain this temperature.

Additionally, on all controls systems except the MDT the control system cycles the cooling output to maintain the supply air temperature within a defined operating window. This window defines the maximum and minimum discharge temperatures.

To change the desired minimum supply or discharge air temperature scroll through the SETPOINTS menu tree, locate the CLG MIN DA Setpoint, and enter a new temperature. This temperature must not be greater than the CLG MAX DA Setpoint. The allowable temperature range is 55°F - 130°F. This sets the lowest discharge air temperature that will leave the unit.

To change the desired maximum supply or discharge air temperature scroll through the SETPOINTS menu tree, locate the CLG MAX DA Setpoint, and enter a new temperature. This temperature must not be less than the CLG MIN DA Setpoint. The allowable temperature range is 55°F - 130°F. This sets the highest discharge air temperature that will leave the unit.

If the maximum and minimum discharge temperature setpoints are set for the same temperature, the supply air temperature will be the same as the setpoint regardless of the room temperature setpoint or actual room temperature.

Damper Control Modes

There are four different modes that control the unit damper operation: Manual, Mixed Air Temperature, Building Pressure, and 100% Outside Air. Except for the 100% Outside Air mode, these operating modes are selected through the menu tree of the local user interface or PC. Not all damper modes are available on all units.

Manual Mode

Manual Mode is the default damper operational mode. This will set the outside air damper to a fixed position.

MDT and MRT Controls. To place the damper operation in Manual Mode on an MDT or MRT control system be sure the appropriate terminals in the unit control panel are not shorted. See the Typical Wiring Schematic and Multiplexed Input sections of this manual for more information. Rotate the damper control knob on the remote panel to the desired percentage of outside air. If the unit served by this control is a direct-fired heater, that recirculates air before the burner, and is

16

Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN

Image 16
Contents Controls Programming Guide JanuaryOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents Unit Operating Modes MDT ControlsMRT Controls MRT-Pro ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes Heating/Ventilating/Cooling Operating Modes Heating ModeGeneral Burner Control Unit Operating Modes Ventilation Mode Cooling Mode M P E R a T U R E S EManual Mode Damper Control ModesMixed Air Temperature Mode Building Pressure Mode Functions 100% Outside AirMinimum Ventilation FreezestatUser Configured PID Control Direct Acting85ºF Reverse Acting Direct actingReverse acting Unit Resets Multiplexed InputsClock Set Critical Fault Codes DiagnosticsFault Code Low Discharge Temperature Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open Fault CODEBurner Status SOLUTIONIf fan is running check prior alarm logFault Code Burner Hand Diagnostics Non-Critical Fault Codes Fault Code Flame FailureSolution If fan is running Fault Code Unit off/Fan onSolution If fan is not running SOLUTIONIf fan/motor is running Fault CODEUnit on/Fan offSolution If fan/motor is not running Fault Code Check Airflow Switches Fault Code Clogged Filter Switch SOLUTIONIf clogged filter switch is closingFault CODEEnergy Save Mode SOLUTIONIf setpoints are misadjustedSOLUTIONIf setpoints are not misadjusted Solution If OAT, RoomT or DAT are such that heat is requiredDiagnostics Solution If setpoints are misadjusted Fault CODEInsufficient OASOLUTIONIf heat is desired SOLUTIONIf less outside air is desired Diagnostics Menu Selection Tree for BACview Menu SelectionUnit Modes Hotkey Menu Selection SET Points HotkeyAlarm Hotkey Resets HotkeyAlarm History 64 Most Recent Status Menu HotkeyUser Configurable Output Hotkey Schedules HotkeyClockset Hotkey Help HotkeyFuel Select Hotkey Thermostat Output Curve Ohms Thermistor Output CurveAirflow Station Layout Airflow station layoutZone 583 Controller Specifications Network CommunicationZone 583 Controller Specifications Rnet MRT-Pro or Room Air sensorTypical Wiring Schematic Non-recirculating with evap Dfoa and Dfia model diagramTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane