Trane Direct-Fired Indoor and Outdoor Make-Up Air Units, MUA-SVP01A-EN Mixed Air Temperature Mode

Page 17

Unit Operating Modes

operating in the heating mode, the unit will automatically keep the minimum outside air at 20%. If the outside air drops below 20%, the burner will cycle off. See Minimum Ventilation.

MRT-Pro Controls. To change the damper mode on an MRT-Pro control system requires the use of a BACview or PC. See the section related to the MRT Expert for instructions on how to use the BACview for programming.

MRT-Expert Control. To place the damper operation in Manual Mode scroll through the menu tree, locate the Damper Mode branch and select Manual Pos. Next, scroll through the menu tree, locate the Setpoints branch, select Man Vent SP, and enter the desired damper position. The allowable range is 0% to 100%. If the unit served by this control is a direct-fired heater, that recirculates air before the burner, and is operating in the heating mode, the unit will automatically keep the minimum outside air at 20%. If the outside air drops below 20%, the burner will cycle off. See Minimum Ventilation.

Mixed Air Temperature Mode

The Mixed Air Temperature mode varies the percentages of outside air and return air to maintain a constant mixed air temperature. The AdaptAire controller computes the mixed air temperature using the outside air and return air temperatures and the ratio of their respective airflows.

MDT and MRT Controls. To place the damper operation in Mixed Air Temperature Mode on an MDT or MRT control system be sure the appropriate terminals in the unit control panel are shorted. See the Typical Wiring Schematic and Multiplexed Input sections of this manual for more information. Rotate the damper control knob on the remote panel to the desired mixed air temperature. If the unit served by this control is a direct-fired heater, that recirculates air before the burner, and is operating in the heating mode, the unit will automatically keep the minimum outside air at 20%. If the outside air drops below 20%, the burner will cycle off. See Minimum Ventilation.

MRT-Pro Controls. To change the damper mode on an MRT-Pro control system requires the use of a BACview or PC. See the section related to the MRT Expert for instructions on how to use the BACview for programming.

MRT-Expert Control. To place the damper operation in Mixed Air Temperature Mode scroll through the menu tree, locate the Damper Mode branch and select MA Temp Ctrl. Next, scroll through the menu tree, locate the Setpoints branch, select Mixed Air, and enter the desired temperature. The allowable range is 30°F - 80°F. If the unit served by this control is a direct-fired heater, that recirculates air before the burner, and is operating in the heating mode, the unit will automatically keep the minimum outside air at 20%. If the outside air drops below 20%, the burner will cycle off. See Minimum Ventilation.

MUA-SVP01A-ENDirect-Fired Indoor and Outdoor Units

17

Image 17
Contents January Controls Programming GuideOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents MDT Controls Unit Operating ModesMRT-Pro Controls MRT ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes General Burner Control Heating ModeHeating/Ventilating/Cooling Operating Modes Unit Operating Modes Ventilation Mode M P E R a T U R E S E Cooling ModeDamper Control Modes Manual ModeMixed Air Temperature Mode Building Pressure Mode 100% Outside Air FunctionsMinimum Ventilation FreezestatDirect Acting User Configured PID Control85ºF Direct acting Reverse ActingReverse acting Multiplexed Inputs Unit ResetsClock Set Fault Code Low Discharge Temperature DiagnosticsCritical Fault Codes Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open SOLUTIONIf fan is running check prior alarm log Fault CODEBurner StatusFault Code Burner Hand Fault Code Flame Failure Diagnostics Non-Critical Fault CodesSolution If fan is not running Fault Code Unit off/Fan onSolution If fan is running Solution If fan/motor is not running Fault CODEUnit on/Fan offSOLUTIONIf fan/motor is running Fault Code Check Airflow Switches SOLUTIONIf clogged filter switch is closing Fault Code Clogged Filter SwitchSOLUTIONIf setpoints are misadjusted Fault CODEEnergy Save ModeSolution If OAT, RoomT or DAT are such that heat is required SOLUTIONIf setpoints are not misadjustedDiagnostics SOLUTIONIf heat is desired Fault CODEInsufficient OASolution If setpoints are misadjusted SOLUTIONIf less outside air is desired Diagnostics Unit Modes Hotkey Menu SelectionMenu Selection Tree for BACview SET Points Hotkey Menu SelectionResets Hotkey Alarm HotkeyAlarm History 64 Most Recent Status Menu HotkeySchedules Hotkey User Configurable Output HotkeyHelp Hotkey Clockset HotkeyFuel Select Hotkey Ohms Thermistor Output Curve Thermostat Output CurveAirflow station layout Airflow Station LayoutNetwork Communication Zone 583 Controller SpecificationsRnet MRT-Pro or Room Air sensor Zone 583 Controller SpecificationsNon-recirculating with evap Dfoa and Dfia model diagram Typical Wiring SchematicTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane