Trane MUA-SVP01A-EN, Direct-Fired Indoor and Outdoor Make-Up Air Units Building Pressure Mode

Page 18

Unit Operating Modes

Building Pressure Mode

The Building Pressure mode varies the percentages of outside air and return air to maintain a constant pressure within the space. A pressure transducer compares the pressure outside the space to the pressure inside the space and transmits a corresponding signal to the AdaptAire controller. The controller compares this signal to the desired building pressure setpoint and uses a PID loop to modulate the outside air and return air dampers to maintain the specified building pressure.

MDT and MRT Controls. The MDT and MRT control systems do not support building pressure control mode.

MRT-Pro Controls. To change the damper mode on an MRT-Pro control system requires the use of a BACview or PC. See the section related to the MRT Expert for instructions on how to use the BACview for programming.

MRT-Expert Control. To place the damper operation in Building Pressure Mode scroll through the menu tree, locate the Damper Mode branch and select Bldg Prs Ctrl. Next, scroll through the menu tree, locate the Setpoints branch, select Bldg Prs, and enter the desired pressure. The allowable range is -0.05"wc to +0.05"wc. If the unit served by this control is a direct-fired heater, that recirculates air before the burner, and is operating in the heating mode, the unit will automatically keep the minimum outside air at 20%. If the outside air drops below 20%, the burner will cycle off. See Minimum Ventilation.

18

Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN

Image 18
Contents Controls Programming Guide JanuaryOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents Unit Operating Modes MDT ControlsMRT Controls MRT-Pro ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes Heating Mode Heating/Ventilating/Cooling Operating ModesGeneral Burner Control Unit Operating Modes Ventilation Mode Cooling Mode M P E R a T U R E S EManual Mode Damper Control ModesMixed Air Temperature Mode Building Pressure Mode Minimum Ventilation Functions100% Outside Air FreezestatUser Configured PID Control Direct Acting85ºF Reverse Acting Direct actingReverse acting Unit Resets Multiplexed InputsClock Set Diagnostics Critical Fault CodesFault Code Low Discharge Temperature Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open Fault CODEBurner Status SOLUTIONIf fan is running check prior alarm logFault Code Burner Hand Diagnostics Non-Critical Fault Codes Fault Code Flame FailureFault Code Unit off/Fan on Solution If fan is runningSolution If fan is not running Fault CODEUnit on/Fan off SOLUTIONIf fan/motor is runningSolution If fan/motor is not running Fault Code Check Airflow Switches Fault Code Clogged Filter Switch SOLUTIONIf clogged filter switch is closingFault CODEEnergy Save Mode SOLUTIONIf setpoints are misadjustedSOLUTIONIf setpoints are not misadjusted Solution If OAT, RoomT or DAT are such that heat is requiredDiagnostics Fault CODEInsufficient OA Solution If setpoints are misadjustedSOLUTIONIf heat is desired SOLUTIONIf less outside air is desired Diagnostics Menu Selection Menu Selection Tree for BACviewUnit Modes Hotkey Menu Selection SET Points HotkeyAlarm History 64 Most Recent Alarm HotkeyResets Hotkey Status Menu HotkeyUser Configurable Output Hotkey Schedules HotkeyClockset Hotkey Help HotkeyFuel Select Hotkey Thermostat Output Curve Ohms Thermistor Output CurveAirflow Station Layout Airflow station layoutZone 583 Controller Specifications Network CommunicationZone 583 Controller Specifications Rnet MRT-Pro or Room Air sensorTypical Wiring Schematic Non-recirculating with evap Dfoa and Dfia model diagramTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane