Trane MUA-SVP01A-EN manual Menu Selection, SET Points Hotkey

Page 44

Menu Selection

Status

Alarm

SET POINTS HOTKEY - 3

Htg Occupied

°F

range 55-90

 

 

 

Htg Setback

°F

range 40-80

 

 

 

Htg Min DA

°F

range 40-130

 

 

 

Htg Max DA

°F

range 55-130

 

 

 

Clg Occupied

°F

range 61-96

 

 

 

Clg Setback

°F

range 75-130

 

 

 

Clg Min DA

°F

range 40-130

 

 

 

Clg Max DA

°F

range 55-130

 

 

 

Man Vent

%OA

range 0-100

 

 

 

Mixed Air

°F

range 30-80

 

 

 

Bldg Prs

"WC

range -0.05-+0.05

 

 

 

Min Vent

%

range 0-100

 

 

 

Economizer Temp

°F

range 40-80

 

 

 

Freeze Stat

°F

range 35-80

 

 

 

Home

 

 

 

 

 

Status

 

 

 

 

 

Alarm

 

 

 

 

 

Resets

 

 

 

 

 

44

Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN

Image 44
Contents Controls Programming Guide JanuaryOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents Unit Operating Modes MDT ControlsMRT Controls MRT-Pro ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes General Burner Control Heating ModeHeating/Ventilating/Cooling Operating Modes Unit Operating Modes Ventilation Mode Cooling Mode M P E R a T U R E S EManual Mode Damper Control ModesMixed Air Temperature Mode Building Pressure Mode Functions 100% Outside AirMinimum Ventilation FreezestatUser Configured PID Control Direct Acting85ºF Reverse Acting Direct actingReverse acting Unit Resets Multiplexed InputsClock Set Fault Code Low Discharge Temperature DiagnosticsCritical Fault Codes Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open Fault CODEBurner Status SOLUTIONIf fan is running check prior alarm logFault Code Burner Hand Diagnostics Non-Critical Fault Codes Fault Code Flame FailureSolution If fan is not running Fault Code Unit off/Fan onSolution If fan is running Solution If fan/motor is not running Fault CODEUnit on/Fan offSOLUTIONIf fan/motor is running Fault Code Check Airflow Switches Fault Code Clogged Filter Switch SOLUTIONIf clogged filter switch is closingFault CODEEnergy Save Mode SOLUTIONIf setpoints are misadjustedSOLUTIONIf setpoints are not misadjusted Solution If OAT, RoomT or DAT are such that heat is requiredDiagnostics SOLUTIONIf heat is desired Fault CODEInsufficient OASolution If setpoints are misadjusted SOLUTIONIf less outside air is desired Diagnostics Unit Modes Hotkey Menu SelectionMenu Selection Tree for BACview Menu Selection SET Points HotkeyAlarm Hotkey Resets HotkeyAlarm History 64 Most Recent Status Menu HotkeyUser Configurable Output Hotkey Schedules HotkeyClockset Hotkey Help HotkeyFuel Select Hotkey Thermostat Output Curve Ohms Thermistor Output CurveAirflow Station Layout Airflow station layoutZone 583 Controller Specifications Network CommunicationZone 583 Controller Specifications Rnet MRT-Pro or Room Air sensorTypical Wiring Schematic Non-recirculating with evap Dfoa and Dfia model diagramTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane