NETWORKING
AdaptAire is adaptable to a variety of different network architectures and protocols. Each controller has
The AdaptAire system can be connected to most existing building automation systems. Some systems may require the use of special controllers and network communication devices. See Appendix I for Device Parameters and Cache Setup information.
ADAPTAIRE DEFAULT SETTINGS
The following is a list of AdaptAire DDC controller defaults. These are the default operating parameters set at the factory prior to shipment.
Table 1. | Default settings |
|
|
|
|
|
|
| ITEM | DEFAULT | RANGE |
|
|
| |
Unit Network Address | 002 binary dips | 000 – 255 binary dips | |
|
|
| |
Unit Operating Mode | OFF | OFF – MANUAL - AUTO | |
|
|
| |
Time Clock Schedule | None | 4 Daily - 12 Holiday - 2 | |
|
|
| Override schedules |
|
|
| |
Heating/Cooling Operating | Heating | HEATING - COOLING | |
| Mode |
|
|
|
|
| |
Damper Operating Mode | Manual | MANUAL - BUILDING | |
|
|
| PRESS - MIXED AIR |
|
|
| TEMP |
|
|
| |
Fuel Selection | Natural Gas | NATURAL - PROPANE | |
|
|
| |
Heating Night Setback | 55°F | 40°F - 80°F | |
|
|
| |
Cooling Night Setback | 100°F | 75°F - 120°F | |
|
|
| |
Room Temperature Setpoint | 65°F | 55°F - 90°F | |
|
|
|
|
| Freezestat | 45°F | 35°F - 50°F |
|
|
| |
Outside Air Economizer | 65°F | 40°F - 80°F | |
| Setpoint |
|
|
|
|
| |
Minimum Discharge | 55°F | 40°F - 130°F | |
Temperature Setpoint |
|
| |
|
|
| |
Maximum Discharge | 100°F | 55°F - 130°F | |
Temperature Setpoint |
|
| |
|
|
| |
Mixed Air Temperature | 50°F | 30°F - 90°F | |
| Setpoint |
|
|
|
|
| |
Building Pressure Setpoint | 0” W. C. | ||
|
|
| |
Manual Damper Position | 20% Outside Air | 0% - 100% | |
| Setpoint |
|
|
|
|
| |
Minimum Ventilation | 20% Outside Air | 0% - 100% | |
| Setpoint |
|
|
|
|
| |
User PID Select | Direct Acting | DIRECT | |
|
|
| |
High Input Value | 0 | ||
|
|
|
|
3 |