Trane Direct-Fired Indoor and Outdoor Make-Up Air Units, MUA-SVP01A-EN manual Networking

Page 3

NETWORKING

AdaptAire is adaptable to a variety of different network architectures and protocols. Each controller has built-in protocol translation and can be configured for operation on ARCnet156 or EIA-485 communication networks. See Appendix IV for specific controller specifications.

The AdaptAire system can be connected to most existing building automation systems. Some systems may require the use of special controllers and network communication devices. See Appendix I for Device Parameters and Cache Setup information.

ADAPTAIRE DEFAULT SETTINGS

The following is a list of AdaptAire DDC controller defaults. These are the default operating parameters set at the factory prior to shipment.

Table 1.

Default settings

 

 

 

 

 

 

 

ITEM

DEFAULT

RANGE

 

 

 

Unit Network Address

002 binary dips

000 – 255 binary dips

 

 

 

Unit Operating Mode

OFF

OFF – MANUAL - AUTO

 

 

 

Time Clock Schedule

None

4 Daily - 12 Holiday - 2

 

 

 

Override schedules

 

 

 

Heating/Cooling Operating

Heating

HEATING - COOLING

 

Mode

 

 

 

 

 

Damper Operating Mode

Manual

MANUAL - BUILDING

 

 

 

PRESS - MIXED AIR

 

 

 

TEMP

 

 

 

Fuel Selection

Natural Gas

NATURAL - PROPANE

 

 

 

Heating Night Setback

55°F

40°F - 80°F

 

 

 

Cooling Night Setback

100°F

75°F - 120°F

 

 

 

Room Temperature Setpoint

65°F

55°F - 90°F

 

 

 

 

 

Freezestat

45°F

35°F - 50°F

 

 

 

Outside Air Economizer

65°F

40°F - 80°F

 

Setpoint

 

 

 

 

 

Minimum Discharge

55°F

40°F - 130°F

Temperature Setpoint

 

 

 

 

 

Maximum Discharge

100°F

55°F - 130°F

Temperature Setpoint

 

 

 

 

 

Mixed Air Temperature

50°F

30°F - 90°F

 

Setpoint

 

 

 

 

 

Building Pressure Setpoint

0” W. C.

-0.05” - +0.05” W. C.

 

 

 

Manual Damper Position

20% Outside Air

0% - 100%

 

Setpoint

 

 

 

 

 

Minimum Ventilation

20% Outside Air

0% - 100%

 

Setpoint

 

 

 

 

 

User PID Select

Direct Acting

DIRECT -REVERSE

 

 

 

High Input Value

0

-9999.99 – 99999.99

 

 

 

 

MUA-SVP01A-ENDirect-Fired Indoor and Outdoor Units

3

Image 3
Contents January Controls Programming GuideOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents MDT Controls Unit Operating ModesMRT-Pro Controls MRT ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes Heating Mode Heating/Ventilating/Cooling Operating ModesGeneral Burner Control Unit Operating Modes Ventilation Mode M P E R a T U R E S E Cooling ModeDamper Control Modes Manual ModeMixed Air Temperature Mode Building Pressure Mode Freezestat Functions100% Outside Air Minimum VentilationDirect Acting User Configured PID Control85ºF Direct acting Reverse ActingReverse acting Multiplexed Inputs Unit ResetsClock Set Diagnostics Critical Fault CodesFault Code Low Discharge Temperature Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open SOLUTIONIf fan is running check prior alarm log Fault CODEBurner StatusFault Code Burner Hand Fault Code Flame Failure Diagnostics Non-Critical Fault CodesFault Code Unit off/Fan on Solution If fan is runningSolution If fan is not running Fault CODEUnit on/Fan off SOLUTIONIf fan/motor is runningSolution If fan/motor is not running Fault Code Check Airflow Switches SOLUTIONIf clogged filter switch is closing Fault Code Clogged Filter SwitchSOLUTIONIf setpoints are misadjusted Fault CODEEnergy Save ModeSolution If OAT, RoomT or DAT are such that heat is required SOLUTIONIf setpoints are not misadjustedDiagnostics Fault CODEInsufficient OA Solution If setpoints are misadjustedSOLUTIONIf heat is desired SOLUTIONIf less outside air is desired Diagnostics Menu Selection Menu Selection Tree for BACviewUnit Modes Hotkey SET Points Hotkey Menu SelectionStatus Menu Hotkey Alarm HotkeyResets Hotkey Alarm History 64 Most RecentSchedules Hotkey User Configurable Output HotkeyHelp Hotkey Clockset HotkeyFuel Select Hotkey Ohms Thermistor Output Curve Thermostat Output CurveAirflow station layout Airflow Station LayoutNetwork Communication Zone 583 Controller SpecificationsRnet MRT-Pro or Room Air sensor Zone 583 Controller SpecificationsNon-recirculating with evap Dfoa and Dfia model diagram Typical Wiring SchematicTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane