I/O Zone 583 Controller Specifications
–LED indication
•3 Analog Outputs
–0 - 10 VDC
OUTPUT ASSIGNMENTS - ANALOG
AO1 | Burner firing rate (to signal conditioner) 0 - 10 VDC |
AO2 | RA or Mixing Damper Control/ User Configured 0 - 10VDC |
AO3 | Unassigned |
OUTPUT ASSIGNMENTS - DIGITAL
DO1 Unit Enable
DO2 Burner Enable
DO3 Cooling Enable
DO4 Alarm
DO5 Pilot to Main Flame Sensor Changeover Switch
INPUT ASSIGNMENTS - UNIVERSAL
IN1 | Pressure Transducer for Building Pressure Control or User Configured |
IN2 Pressure Transducer for Flow Station | |
IN3 | Multiplexed |
•100% Outside Air/100% Output
•Flame Failure Alarm
•Safety Circuit Status
•Manual/Mixed Air Dmpr Control
IN4 Multiplexed
•Auxiliary Unit Enable
•Clogged Filter
•Fan Status
•Burner Status
IN5 Outside Air sensor
IN6 Discharge Air sensor
IN7 Unit Enable/Remote Setpoint
IN8 Damper Control
RNET MRT-Pro or Room Air sensor