Trane Direct-Fired Indoor and Outdoor Make-Up Air Units SOLUTIONIf less outside air is desired

Page 41

Diagnostics

4.Do the dampers track with a change in the %OA setpoint? The dampers utilized on the unit are not linear with respect to airflow and openness, and as such, the proportion of outside air damper movement will not be exactly equal to the %OA setpoint. However, at 20% OA the dampers should be approximately ½" open.

Yes. Continue.

No. Check the damper motor and linkage connections. When 24VAC is powering the damper actuator and the control signal is 0VDC, the outside air damper should be close to a "rattle tight" position and the return air damper should be open. If the 24VAC power is removed, the actuator will draw the outside air damper tightly closed and the return air damper tightly open. When 24VAC is powering the damper actuator and the control signal is 10VDC, the outside air damper should be fully open and the return air damper should be closed.

5.Is there approximately 24VAC at the COM and EXC terminals on the airflow station pressure transducer?

Yes. Continue.

No. Is there 120VAC on the primary side of the low voltage transformer and 24VAC volt at the transformer secondary?

Yes. There is an open in the wiring between the transformer and the transducer. Locate the wiring problem and rectify.

No. If there is 120VAC on the primary and 0VAC on the secondary, replace the transformer. If there is 0VAC on the primary, there is an open in the wiring supplying power to the transformer. Locate the wiring problem and rectify.

6.Remove both of the plastic tubes from the airflow station pressure transducer and gently blow into the HIGH side port. Caution: The transducer is extremely sensitive. Blowing too hard into the sensing tube may damage the transducer. Is there approximately 5VDC across the COM and OUT terminals of the pressure transducer?

Yes. Continue.

No. The pressure transducer is defective. Replace it.

7.Remove both of the plastic tubes from the airflow station pressure transducer and gently blow into the HIGH side port. Caution: The transducer is extremely sensitive. Blowing too hard into the sensing tube may damage the transducer. Is there approximately 5VDC across the controller input terminals that are connected to the transducer?

Yes. There is a problem with the controller. Replace it.

No. There is an open in the wiring between these pressure transducer and the AdaptAire controller terminals. Locate and rectify.

SOLUTION:If less outside air is desired

1.Is heat required?

MUA-SVP01A-ENDirect-Fired Indoor and Outdoor Units

41

Image 41
Contents January Controls Programming GuideOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents MDT Controls Unit Operating ModesMRT-Pro Controls MRT ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes General Burner Control Heating ModeHeating/Ventilating/Cooling Operating Modes Unit Operating Modes Ventilation Mode M P E R a T U R E S E Cooling ModeDamper Control Modes Manual ModeMixed Air Temperature Mode Building Pressure Mode 100% Outside Air FunctionsMinimum Ventilation FreezestatDirect Acting User Configured PID Control85ºF Direct acting Reverse ActingReverse acting Multiplexed Inputs Unit ResetsClock Set Fault Code Low Discharge Temperature DiagnosticsCritical Fault Codes Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open SOLUTIONIf fan is running check prior alarm log Fault CODEBurner StatusFault Code Burner Hand Fault Code Flame Failure Diagnostics Non-Critical Fault CodesSolution If fan is not running Fault Code Unit off/Fan onSolution If fan is running Solution If fan/motor is not running Fault CODEUnit on/Fan offSOLUTIONIf fan/motor is running Fault Code Check Airflow Switches SOLUTIONIf clogged filter switch is closing Fault Code Clogged Filter SwitchSOLUTIONIf setpoints are misadjusted Fault CODEEnergy Save ModeSolution If OAT, RoomT or DAT are such that heat is required SOLUTIONIf setpoints are not misadjustedDiagnostics SOLUTIONIf heat is desired Fault CODEInsufficient OASolution If setpoints are misadjusted SOLUTIONIf less outside air is desired Diagnostics Unit Modes Hotkey Menu SelectionMenu Selection Tree for BACview SET Points Hotkey Menu SelectionResets Hotkey Alarm HotkeyAlarm History 64 Most Recent Status Menu HotkeySchedules Hotkey User Configurable Output HotkeyHelp Hotkey Clockset HotkeyFuel Select Hotkey Ohms Thermistor Output Curve Thermostat Output CurveAirflow station layout Airflow Station LayoutNetwork Communication Zone 583 Controller SpecificationsRnet MRT-Pro or Room Air sensor Zone 583 Controller SpecificationsNon-recirculating with evap Dfoa and Dfia model diagram Typical Wiring SchematicTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane